Table 1 — Positive Pressure SystemAssembly Numbers
POSITIVE PRESSURE
SYSTEMASSEMBLY
NUMBER
PUMPOUT UNIT
ASSEMBLYNO. REFRIGERANT COMPRESSOR MOTOR
(V-Ph-Hz) MAXIMUM
RLA LRA STORAGE
TANK
19XB04280205 19EA42-748 R-22 208-3-60 13.2 63.5 28 cu ft
19XB04280206 19EA44-748 R-22 230-3-60 11.5 57.5 28 cu ft
19XB04280207 19EA46-748 R-22 400/460-3-50/60 5.8 28.8 28 cu ft
19XB04280208 19EA47-748 R-22 575-3-60 4.6 23.0 28 cu ft
19XB04280213 19EA48-748 R-134a 208-3-60 13.2 63.5 28cu ft
19XB04280214 19EA49-748 R-134a 230-3-60 11.5 57.5 28cu ft
19XB04280215 19EA51-748 R-134a 400/460-3-50/60 5.8 28.8 28cu ft
19XB04280216 19EA52-748 R-134a 575-3-60 4.6 23.0 28cu ft
19XB04280601 19EA42-748 R-22 208-3-60 13.2 63.5 None
19XB04280602 19EA44-748 R-22 230-3-60 11.5 57.5 None
19XB04280603 19EA46-748 R-22 400/460-3-50/60 5.8 28.8 None
19XB04280604 19EA47-748 R-22 575-3-60 4.6 23.0 None
19XB04280605 19EA48-658 R-134a 208-3-60 13.2 63.5 None
19XB04280606 19EA49-658 R-134a 230-3-60 11.5 57.5 None
19XB04280607 19EA51-658 R-134a 400/460-3-50/60 5.8 28.8 None
19XB04280608 19EA52-658 R-134a 575-3-60 4.6 23.0 None
19XB04520205 19EA42-748 R-22 208-3-60 13.2 63.5 52 cu ft
19XB04520206 19EA44-748 R-22 230-3-60 11.5 57.5 52 cu ft
19XB04520207 19EA46-748 R-22 400/460-3-50/60 5.8 28.8 52 cu ft
19XB04520208 19EA47-748 R-22 575-3-60 4.6 23.0 52 cu ft
19XB04520213 19EA48-748 R-134a 208-3-60 13.2 63.5 52cu ft
19XB04520214 19EA49-748 R-134a 230-3-60 11.5 57.5 52cu ft
19XB04520215 19EA51-748 R-134a 400/460-3-50/60 5.8 28.8 52cu ft
19XB04520216 19EA52-748 R-134a 575-3-60 4.6 23.0 52cu ft
LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
NOTES:
1. Allstorage vessels are 300 psig (2068 kPa) designs per the ASME
(American Society of Mechanical Engineers) Boiler Pressure
VesselCode, Section VIII Division 1.
2. Allunits above are shipped with a 15 psig (103 kPa) nitrogen charge.
3. Nominal horsepower for all pumpout units is 3.0.
Mountthe Pumpout Unit — Thepumpout unit, if pur-
chasedseparately, may be mounted directly on the chiller or
it may be floor mounted.
MOUNTING ON THE CHILLER — See instructions pro-
videdwith the chiller for mounting the pumpout unit. A typi-
cal chiller mount is shown in Fig. 2.
FLOOR MOUNTING — Select a ventilated and accessible
area,free of traffic or other hazards. Remove and discard the
4angle supports at the base of the pumpout unit and bolt the
unit to the floor through the 4
7
16
in. holes at the base of the
pumpout unit. Special isolation is unnecessary.Contact sur-
face and dimensions for the pumpout unit are given in
Fig. 3.
Rig the Storage Tank— The complete 19XB system
can be rigged as a single assembly.See the rigging instruc-
tions on the label attached to the assembly.Also refer to the
rigging guide (Fig. 4), physical data in Tables2 and 3, and
contact surface and dimensions for the complete system in
Fig. 5. Lift the assembly only fromthe 4 points indicated in
the rigging guide. Each rigging cable must be capable of
supporting the entire weight of the assembly.
Liftingthe assembly from points other than those speci-
fied may result in serious damage to the assembly and
personalinjury. Rigging equipment and procedures must
beadequate for assembly. See Tables 2 and 3 for weights.
NOTE: These weights are broken down into pumpout
unit and storage tank weights. For the complete assem-
bly weight, add all components together.
3