30
Table11 – Altitude Com pensation* (A04--A07)
ELEVATION
ft (m)
72,000 BTUH
Nominal
115,000 BTUH
Nominal
150,000 BTUH
Nominal
NG
Orifice Size
LP
Orifice Size
NG
Orifice Size
LP
Orifice Size
NG
Orifice Size
LP
Orifice Size
0 ---2000 (610) 331514331503†30 463
2000(610) 351514351514†30 473
3000(914) 351524351514311473
4000(1219) 361524361514311483
5000(1524) 361524361514311483
6000(1829) 372524372524311483
7000(2134) 382534382524321493
8000(2438) 392534392524331493
9000(2743) †40 534†40 534341503
10000(3048) †41 544†41 534351503
11000(3353) †42 544†42 534361514
12000(3658) †43 544†43 544372514
13000(3962) †43 554†43 544382524
14000(4267) 442†56 442554†40 534
Table11 (cont.) --Altitude Compensation* (A08 --A12)
ELEVATION
ft (m)
125,000
BTUH Nominal
250,000
BTUH Nominal
180,000, 224,000
BTUH Nominal
NG Orifice
Size
LP Orifice
Size
NG Orifice
Size
LP Orifice
Size
NG Orifice
Size
LP Orifice
Size
0 ---2000 (610) 311493†30 463311483
2000(610) 321503†30 473321493
3000(914) 321503311473321493
4000(1219) 331503311483331493
5000(1524) 331514311483331503
6000(1829) 341514311483341503
7000(2134) 351514321493351503
8000(2438) 361524331493361514
9000(2743) 372524341503372514
10000(3048) 382524351503382524
11000(3353) 392534361514392524
12000(3658) †41 534372514†41 534
13000(3962) †42 544382524†42 534
14000(4267) †43 544†40 534†43 544
LEGEND
NG= Natural Gas LP= Liquid Propane
* As the height above sea level increases, there isless oxygen
percubic ft. of air. Therefore,heat input rate should be reduced
athigher altitudes.
{Notincluded in kit. May be purchasedseparately through
dealer.
1= CRLP ELEV001A00
2= CRLP ELEV002A00
3= CRLP ELEV003A00
4= CRLP ELEV004A00
48TC