55
7. Verify proper wiring between the BAS and the con-
troller.
8. Verifythat the BAS is reading or writing to the proper
Modbus register numbers on the controller. Download
the latest pointslist for the controller to verify.
9. Verify that the BAS is sending his requests to the
proper slave address of our controller.
NOTE: See RTU--MP 3rd Party Integration Guide (or
alternatively Form 48--50H--T--1T,Appendix) for Modbus
Protocol Conformance Statement.

N2

1. Verify that the BAS and controller are both set to
speak the N2 protocol.The protocol of the controller
is set via SW3 (switches 3, 4, 5, and 6). The protocol
can also be verified by getting a Modstat of the con-
troller through the BACview. Hit the “FN” key and
the ’.’ key at the same time to pull up a Modstat.
Scroll to the bottom ofthe page and there is a section
entitled ”Network Communications.”The active pro-
tocol and baud rate will be shown in this section.
2. Verify that the BAS and controller are set for 9600
baud. The baud rate of the controller is set via SW3
(switches1 and 2). The baud rate can also be verified
via the BACview by obtaining a Modstat (see above).
3. Verify that the BAS is configured to speak 2--wire
EIA--485to the controller.The BAS may have to con-
figure jumper or DIP switches on their end.
4. Verify that the BASa ndt he controller have the same
communication settings (8 data bits, No Parity,and 1
stop bit).
5. Verify that the controller has a unique N2 slave ad-
dress on the N2 bus. The controller’s N2 slave ad-
dress is set by its rotary address switches.
6. Verify proper wiring between the BAS and the con-
troller.
7. Verifythat the BAS is reading or writing to the proper
network point addresses on the controller. Download
the latest pointslist for the controller to verify.
8. Verify that the BAS is sending his requests to the
proper slave address of our controller.
NOTE: See RTU--MP 3rd Party Integration Guide (or
alternatively Form 48--50H--T--1T Appendix) for N2
Protocol Conformance Statement.
ECONOMIZER SYSTEMS
The 48TC units may be equipped with a factory--installed
or accessory (field--installed) economizer system. Two
types are available: with a logic control system
(EconoMi$er IV) and without a control system
(EconoMi$er2, for use with external control systems such
as PremierLink). See Fig. 70 and Fig. 71 for component
locations on each type. See Fig. 72 and Fig. 73 for
economizer sectionwiring diagrams.
Both EconoMi$ers use direct--drivedamper actuators.
ECONOMI$ER IV
CONTROLLER
OUTSIDE AIR
TEMPERATURE SENSOR
LOW AMBIENT
SENSOR
A
CTUATOR
WIRING
HARNESS
C06021
Fig. 70 --EconoMi$er IV Component Locations
ECONOMI$ER2
PLUG
BAROMETRIC
RELIEF
DAMPER
OUTDOOR
AIR HOOD
HOOD
SHIPPING
BRACKET
GEAR DRIVEN
DAMPER
C06022
Fig. 71 --EconoMi$er2 Component Locations
48TC