125,000/90,000 BTUH INPUT
180,000/120,000 BTUH INPUT
240,000/180,000 BTUH INPUT
250,000/200,000 BTUH INPUT
C08447
Fig. 36 --Spark Adjustment (08--12)
Table8 – LED Error Code De scription*
LEDINDICATION ERRORCODE
DESCRIPTION
ON NormalOperation
OFF HardwareFailure
1Flash{EvaporatorFanOn/Off Delay Modified
2Flashes LimitSwitch Fault
3Flashes Flame Sense Fault
4Flashes 4 Consecutive Limit Switch Faults
5Flashes Ignition Lockout Fault
6Flashes Induced---DraftMotor Fault
7Flashes RolloutSwitch Fault
8Flashes InternalControl Fault
9Flashes Software Lockout
LEGEND
LED --- Li g h t Em i t t i n g Di o d e
* A3 ---secondpause exists between LED error code flashes. If.
morethan one error code exists, all applicable codes willb e
displayed in numerical sequence.
{Indicatesa code that is not an error.The unit will continue to
operatewhen this code is displayed.
IMPORTANT: Refer to Troubleshooting Table 13 and
Table14 for a dditional information.
OrificeReplacement
This unit uses orifice type LH32RFnnn (where nnn
indicates orifice reference size). When replacing unit
orifices, order the necessary parts via Carrier RCD.See
Table 10 for available orifice sizes. See Table 11 and
Table 12 for orifice sizes for Natural Gas and LP fuel
usage at various elevations above sea level.
Check that each replacementorifice is tight at its threads
into the manifold pipe and that orificeprojection does not
exceed maximum value.See Fig. 32.
48TC