48TC

Table 24 – Manufacture Date

When troubleshooting, you may need to know a control module’s manufacture date

Obtain the manufacture date from

Notes

 

a...

 

 

Module status report (modstat)

To obtain a modstat with BACview6:

 

1. Press Function (FN) key and hold.

 

2. Then press period (.)

 

3. Release both buttons.

 

The report shows the date under Main board hardware.

Sticker on the back of the main control

The serial numbers are unique and contain embedded information:

module board

“RMP”

--- These first three digits are unique to RTU---MP and are used as an identifier.

”Serial No: RMPYMxxxxN”

“YM”

--- These two digits identify the last digit of the year and month (in hex, A=10/Oct)

(Bar Coded & Typed Number)

xxxx”

of manufacture. ”74” would represent a date of manufacture of ”April 2007”.

 

--- These four digits represent the sequential number of units produced for a given

 

“N”

product for the mentioned manufacturing time period.

 

--- This final digit represents the decade and toggles between ”N” and ”M” every

 

 

ten years.

Table 25 – Basic Protocol Troubleshooting

Problem

Possible cause

Corrective action

No communication with 3rd

Incorrect settings on SW1, SW2 and SW3

Verify and correct switch settings. Cycle

party vendor

 

power to RTU---MP after changing switch

 

 

settings.

 

RS485 Port has no voltage output

Verify RTU---MP has correct power supply

 

(check with RTU---MP disconnected from RS485 commu-

Possible bad driver on board.

 

nication bus)

 

 

Bacnet @ 9600/19.2K --- .01 to .045vdc

Check RS485 bus for external before re-

 

 

connecting to the bus

 

Bacnet @ 38.4K --- .06 to .09vdc

Voltage, shorts or grounding

 

Bacnet @ 76.8K --- .1vdc

before reconnecting to the bus

 

Modbus @ 9600 --- 76.8K --- .124vdc

 

 

N2 @ 9600 --- .124vdc

 

 

Verify devices are daisy chained and repeaters and bias

Check 3rd party vendor RS485 commu-

 

terminators are correctly installed

nication wiring guidelines and trouble-

 

 

shooting procedures

S MaxInfo Frames: This property defines the maximum number of responses that will be sent when our controller gets the token. A valid number is any positive integer. The default is 10 and should be ideal for the majority of applications. In cases where the controller is the target of many requests, this number could be increased as high as 100 or 200.

NOTE: MS/TP networks can be comprised of both Master and Slave nodes. Valid MAC addresses for Master nodes are 0 - 127 and valid addresses for Slave nodes are 0 - 254.

NOTE: See RTU-MP 3rd Party Integration Guide (or alternatively Form 48-50H-T-1T Appendix) for Protocol Maps.

Table 26 – Modbus Exception Codes that May be

Returned From This Controller

CODE

NAME

MEANING

 

 

 

 

 

The Modbus function code used

01

Illegal Function

in the query is not supported by

 

 

the controller.

 

 

 

 

 

The register address used in the

02

Illegal Data Address

query is not supported by the

 

 

controller.

 

 

 

 

 

The Modbus Master has at-

04

Slave Device Failure

tempted to write to a non---exist-

 

 

ent register or a read---only regis-

 

 

ter in the controller.

 

 

 

Modbus

1.Verify that the BAS and controller are both set to speak the Modbus RTU protocol. The protocol of the controller is set via SW3 (switches 3, 4, 5, and 6). The protocol can also be verified by getting a Modstat of the controller through the BACview. Hit the ”FN” key and the ’.’ key at the same time to pull up a Modstat. Scroll to the bottom of the page and there is a section entitled “Network Communications.” The active protocol and baud rate will be shown in this section.

2.Verify that the BAS and controller are set for the same baud rate. The baud rate of the controller is set via SW3 (switches 1 and 2). The baud rate can also be verified via the BACview by obtaining a Modstat (see above).

3.Verify that the BAS is configured to speak 2-wire EIA-485 to the controller. The BAS may have to con- figure jumper or DIP switches on their end.

4.Verify that the BAS and the controller have the same communication settings (8 data bits, No Parity, and 1 stop bit).

5.Verify that the controller has a unique Modbus slave address. The controller’s Modbus slave address is set by its rotary address switches.

6.Verify that the BAS is using the proper Modbus func- tion codes to access data from our controller. Sup- ported function codes are shown above.

54

Page 54
Image 54
Carrier 48TCA04---A12 appendix Modbus, Manufacture Date, Basic Protocol Troubleshooting, Code Name Meaning

48TCA04---A12 specifications

The Carrier 48TCA04---A12 is a high-efficiency rooftop air conditioning unit designed for commercial and industrial applications. Known for its reliability and performance, this model features advanced technologies that cater to diverse climate control needs.

One of the standout features of the Carrier 48TCA04---A12 is its excellent energy efficiency, which adheres to the stringent standards set by the U.S. Environmental Protection Agency. The unit utilizes a highly efficient scroll compressor combined with state-of-the-art heat exchanger technology, allowing it to operate with minimal energy consumption while providing powerful cooling capabilities.

The unit comes equipped with a robust and durable design, built to withstand various environmental conditions. Its weather-resistant cabinet is constructed from high-quality materials, ensuring long-lasting performance even in harsh climates. Additionally, the unit features a galvanized steel structure with a powder-coated finish, further enhancing its resistance to corrosion and wear.

In terms of technologies, the Carrier 48TCA04---A12 incorporates advanced controls that promote optimal performance. The unit supports Carrier's smart connectivity options, facilitating remote monitoring and adjustments via smart devices. This feature ensures convenient energy management and allows maintenance teams to access performance data, leading to proactive service interventions.

Another important characteristic of this unit is its quiet operation. The design includes sound-reducing insulation and a well-engineered airflow system, minimizing noise levels to create a more comfortable indoor environment. This is particularly important for commercial spaces such as offices and retail environments, where a tranquil atmosphere is critical for customer satisfaction and productivity.

The Carrier 48TCA04---A12 also offers diverse application flexibility, making it suitable for various locations, from small retail stores to large warehouses. With several tonnage options available, users can select a model that perfectly aligns with their specific cooling needs. Additionally, the unit can be easily integrated with existing HVAC systems, providing a seamless solution for upgrading or retrofitting older installations.

To sum up, the Carrier 48TCA04---A12 rooftop air conditioning unit stands out due to its exceptional energy efficiency, durable construction, advanced technology, and quiet operation, making it a reliable choice for commercial and industrial cooling solutions. Its flexibility and smart technology integrations ensure that it meets a wide range of climate control requirements effectively.