Table 21 – RTU-MP Controller Inputs and Outputs

 

 

POINT NAME

BACnet OBJECT

 

TYPE OF I/O

CONNECTION PIN

 

 

NAME

 

NUMBERS

 

 

 

 

 

 

 

 

INPUTS

 

 

 

Space Temperature Sensor

sptsens

 

AI (10K Thermistor)

J20---1, 2

Supply Air Temperature

sat

 

AI (10K Thermistor)

J2---1, 2

Local Outside Air Temperature Sensor

oatsens

 

AI (10K Thermistor)

J2---3, 4

Space Temperature Offset Pot

sptopot

 

AI (100K Potentiometer)

J20---3

Indoor Air Quality

iaq

 

AI (4---20 ma)

J4---2, 3

Outdoor Air Quality

oaq

 

AI (4---20 ma)

J4---5, 6

Safety Chain Feedback

safety

 

DI (24 VAC)

J1---9

Compressor Safety

compstat

 

DI (24 VAC)

J1---2

Fire Shutdown

firedown

 

DI (24 VAC)

J1---10

Enthalpy Switch

enthalpy

 

DI (24 VAC)

J2---6, 7

Humidistat Input Status

humstat

 

DI (24 VAC)

J5---7, 8

 

 

 

CONFIGURABLE

INPUTS*

 

Space Relative Humidity

sprh

 

AI (4---20 ma)

J4---2,3 or J4---5,6

Outside Air Relative Humidity

oarh

 

AI (4---20 ma)

 

 

Supply Fan Status

fanstat

 

DI (24 VAC)

J5---1,2 or J5---3,4 or

Filter Status

filtstat

 

DI (24 VAC)

 

J5 5,6 or J5---7,8

Remote Occupancy Input

remocc

 

DI (24 VAC)

 

 

 

 

 

OUTPUTS

 

 

 

Economizer Commanded Position

econocmd

 

4---20ma

J2---5

Supply Fan Relay State

sf

 

DO Relay (24VAC , 1A)

J1---4

Compressor 1 Relay State

comp_1

 

DO Relay (24VAC , 1A)

J1---8

Compressor 2 Relay State

comp_2

 

DO Relay (24VAC , 1A)

J1---7

Heat Stage 1 Relay State

heat_1

 

DO Relay (24VAC , 1A)

J1---6

Heat Stage 2 Relay State

heat_2

 

DO Relay (24VAC , 1A)

J1---5

Power Exhaust Relay State

aux_2

 

DO Relay (24VAC , 1A)

J11---3

Dehumidification Relay State

humizer

 

DO Relay (24VAC, 1A)

J11---7, 8

LEGEND

 

 

 

 

AI

---

Analog Input

 

 

 

 

AO ---

Analog Output

 

 

 

 

DI

---

Discrete Input

 

 

 

 

DO ---

Discrete Output

 

 

 

 

*These inputs (if installed) take the place of the default input on the specific channel according to schematic. Parallel pins J5---1 = J2---6, J5---3 = J1---10, J5---5 = J1---2 are used for field---installation.

Refer to the input configuration and accessory sections for more detail.

48TC

NOTE: Refer to Form 48-50H-T-2T for complete configuration of RTU-MP, operating sequences and troubleshooting information. Refer to RTU-MP 3rd Party Integration Guide for details on configuration and troubleshooting of connected networks. Have a copy of these manuals available at unit start-up.

The RTU-MP controller requires the use of a Carrier space sensor. A standard thermostat cannot be used with the RTU-MP system.

Supply Air Temperature (SAT) Sensor - On FIOP-equipped 48TC unit, the unit is supplied with a supply-air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6-inches (12.7

mm)in length. It is a nominal 10-k ohm thermistor. See Table 15 for temperature-resistance characteristic.

The SAT is factory-wired. The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2-in. hole in the flange or duct.

Use two field-supplied, self-drilling screws to secure the sensor probe in a horizontal orientation. See Fig. 41.

Outdoor Air Temperature (OAT) Sensor - The OAT is factory-mounted in the EconoMi$er 2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring. See Table 15 for temperature-resistance characteristic.

EconoMi$er 2 - The RTU-MP control is used with EconoMi$er2 (option or accessory) for outdoor air management. The damper position is controlled directly by the RTU-MP control; EconoMi$er 2 has no internal logic device.

Outdoor air management functions can be enhanced with field-installation of these accessory control devices:

Enthalpy control (outdoor air or differential sensors) Space CO2 sensor

Outdoor air CO2 sensor

Field Connections - Field connections for accessory sensors and input devices are made the RTU-MP, at plugs J1, J2, J4, J5, J11 and J20. All field control wiring that

45

Page 45
Image 45
Carrier 48TCA04---A12 appendix RTU-MP Controller Inputs and Outputs

48TCA04---A12 specifications

The Carrier 48TCA04---A12 is a high-efficiency rooftop air conditioning unit designed for commercial and industrial applications. Known for its reliability and performance, this model features advanced technologies that cater to diverse climate control needs.

One of the standout features of the Carrier 48TCA04---A12 is its excellent energy efficiency, which adheres to the stringent standards set by the U.S. Environmental Protection Agency. The unit utilizes a highly efficient scroll compressor combined with state-of-the-art heat exchanger technology, allowing it to operate with minimal energy consumption while providing powerful cooling capabilities.

The unit comes equipped with a robust and durable design, built to withstand various environmental conditions. Its weather-resistant cabinet is constructed from high-quality materials, ensuring long-lasting performance even in harsh climates. Additionally, the unit features a galvanized steel structure with a powder-coated finish, further enhancing its resistance to corrosion and wear.

In terms of technologies, the Carrier 48TCA04---A12 incorporates advanced controls that promote optimal performance. The unit supports Carrier's smart connectivity options, facilitating remote monitoring and adjustments via smart devices. This feature ensures convenient energy management and allows maintenance teams to access performance data, leading to proactive service interventions.

Another important characteristic of this unit is its quiet operation. The design includes sound-reducing insulation and a well-engineered airflow system, minimizing noise levels to create a more comfortable indoor environment. This is particularly important for commercial spaces such as offices and retail environments, where a tranquil atmosphere is critical for customer satisfaction and productivity.

The Carrier 48TCA04---A12 also offers diverse application flexibility, making it suitable for various locations, from small retail stores to large warehouses. With several tonnage options available, users can select a model that perfectly aligns with their specific cooling needs. Additionally, the unit can be easily integrated with existing HVAC systems, providing a seamless solution for upgrading or retrofitting older installations.

To sum up, the Carrier 48TCA04---A12 rooftop air conditioning unit stands out due to its exceptional energy efficiency, durable construction, advanced technology, and quiet operation, making it a reliable choice for commercial and industrial cooling solutions. Its flexibility and smart technology integrations ensure that it meets a wide range of climate control requirements effectively.