If the calculated IAQ minimum position is greater than
the IAQ maximum damper position configurationthen it
will be clamped to the configured value.
Demand Limit
If the RTU--MP receives a level 1 (one degree offset), 2
(two degree offset), or a 3 (4 degree offset) to the BACnet
demand limit variable, the controller will expand the
heating and cooling setpoints by the configured demand
limit setpoint value and remain in effectuntil the BACnet
demand limit variable receivesa 0 value.
FASTENERTORQUE VALUES
See Table32 for torque val ues.
Table32 – Torque Values
Supplyfan m otormounting 12 0 +/ --- 1 2 in ---l b s
Supply fan motor adjustment plate 12 0 +/ --- 1 2 in ---l b s
Motor pulley setscrew 72+/---5 in ---lbs
Fanp ulley setscrew 72+/---5 in ---lbs
Blowerwheel hub setscrew 72+/--- 5 in---lbs
Bearing locking collar setscrew 65 --- 70 in --- lbs
Compressor mounting bolts 65 --- 75 in --- lbs
Condenserfan motor mounting bolts 20 + /--- 2 i n--- lb s
Condenserfan hub setscrew 84 + / --- 12 in--- lbs