Carrier 48TJF008-012, 48TJE008-014 Condenser-FanAdjustment Fig, Ð Condenser-FanAdjustment

Models: 48TJF008-012 48TJD008-014 48TJE008-014

1 40
Download 40 pages 31.89 Kb
Page 26
Image 26
Condenser-Fan Adjustment (Fig. 40)

Condenser-Fan Adjustment (Fig. 40)

1.Shut off unit power supply.

2.Remove condenser-fan assembly (grille, motor, motor cover, and fan) and loosen fan hub setscrews.

3.Adjust fan height as shown in Fig. 40.

4.Tighten setscrews and replace condenser-fan assembly.

48TJ UNIT VOLTAGE

FAN HEIGHT ``A'' (in.)

208/230 V

2.75

460 V and 575 V

3.50

Fig. 40 Ð Condenser-Fan Adjustment

Manual Outdoor-Air Damper Ð If outdoor-air damper blade is required, see Manual Outdoor-Air Damper section on page 11.

Economizer Adjustment Ð Refer to Optional Econo- mizer sections on pages 12 and 15.

Condenser Coil Grille Ð Condenser coil grille is shipped factory-installed. No adjustments are required.

Refrigerant Charge Ð Amount of refrigerant charge is listed on unit nameplate (also refer to Table 1). Refer to Carrier GTAC 2-5 Charging, Recovery, Recycling, and Rec- lamation training manual and the following procedures.

Unit panels must be in place when unit is operating dur- ing charging procedure.

NO CHARGE Ð Use standard evacuating techniques. After evacuating system, weigh in the speci®ed amount of refrig- erant (refer to Table 1).

LOW CHARGE COOLING Ð Using Cooling Charging Charts, Fig. 41-44, vary refrigerant until the conditions of the appropriate chart are met. Note the charging charts are different from the type normally used. The charts are based on charging the units to the correct superheat for the various operating conditions. Accurate pressure gage and tempera- ture sensing device are required. Connect the pressure gage

to the service port on the suction line. Mount the tempera- ture sensing device on the suction line and insulate it so that outdoor ambient temperature does not affect the reading. Indoor- air cfm must be within the normal operating range of the unit.

TO USE COOLING CHARGING CHART Ð Take the out- door ambient temperature and read the suction pressure gage. Refer to appropriate chart to determine what suction tem- perature should be. If suction temperature is high, add re- frigerant. If suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as charge is ad- justed. Example (Fig. 44, Circuit 2):

Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . 85 F Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 psig Suction Temperature should be . . . . . . . . . . . . . . . . . . 56 F (Suction temperature may vary ± 5 F.)

If Chargemaster charging device is used, temperature and pressure readings must be accomplished using the charging charts.

Fig. 41 Ð Cooling Charging Chart; 48TJ008

26

Page 26
Image 26
Carrier 48TJF008-012 Condenser-FanAdjustment Fig, Ð Condenser-FanAdjustment, Ð Cooling Charging Chart 48TJ008