TROUBLESHOOTING
Table 17 Ð LED Error Code Service Analysis
PROBLEM | CAUSE | REMEDY |
Hardware failure. | Loss of power to control module (IGC). | Check |
(LED OFF) |
| breaker, and transformer. Units without a |
|
| breaker have an internal overload in the |
|
| former. If the overload trips, allow 10 minutes for auto- |
|
| matic reset. |
Limit switch fault. | High temperature limit switch is open. | Check the operation of the indoor (evaporator) fan mo- |
(LED 2 ¯ashes) |
| tor. Ensure that the |
|
| cordance with the range on the unit nameplate. |
Flame sense fault. | The IGC sensed ¯ame that should not be present. | Reset unit. If problem persists, replace control board. |
(LED 3 ¯ashes) |
|
|
4 consecutive limit | Inadequate air¯ow to unit. | Check operation of indoor (evaporator) fan motor and |
switch trips. |
| that |
(LED 4 ¯ashes) |
| unit nameplate information. |
Ignition lockout. | Unit unsuccessfully attempted ignition for 15 minutes. | Check ignitor and ¯ame sensor electrode spacing, gaps, |
(LED 5 ¯ashes) |
| etc. Ensure that ¯ame sense and ignition wires are prop- |
|
| erly terminated. Verify that unit is obtaining proper |
|
| amount of gas. |
IGC does not sense that | Check for proper voltage. If motor is operating, check | |
fault. | operating. | the speed sensor plug/IGC Terminal J2 connection. |
(LED 6 ¯ashes) |
| Proper connection: PIN 1 Ð White, PI N 2 Ð Red, PIN 3 |
|
| Ð Black. |
Rollout switch fault. | Rollout switch has opened. | Rollout switch will automatically reset, but IGC will con- |
(LED 7 ¯ashes) |
| tinue to lock out unit. Check gas valve operation. Ensure |
|
| that |
|
| motor shaft. Reset unit at unit disconnect. |
Internal control fault. | Microprocessor has sensed an error in the software or | If error code is not cleared by resetting unit power, re- |
(LED 8 ¯ashes) | hardware. | place the IGC. |
LEGEND
IGC Ð Integrated Gas Unit Controller
LED Ð
If the IGC must be replaced, be sure to ground yourself to dis- sipate any electrical charge that may be present before han- dling new control board. The IGC is sensitive to static electricity and may be damaged if the necessary precautions are not taken.
IMPORTANT: Refer to Table 21 Ð Heating Service Troubleshoot- ing for additional troubleshooting information.