dampers should be fully closed. Turn the potentiom- eter gradually counterclockwise until the desired po- sition is reached.
c.Connect T and T1 to the 24 v power supply.
d.After installation is complete, calculate the mini- mum air¯ow across the economizer. To calculate the minimum air¯ow, the following data is needed: total
cfm (cfm3), temperature of the total cfm (T3), tem- perature of the return air (T1), and temperature of the entering outside air (T2). Cfm1 is the return air cfm, which will be the minimum air¯ow.
Insert the data into the following equations:
T1 | (cfm1) + T2 | (cfm2) |
| = T3 | ||
|
| cfm3 |
|
| ||
|
|
|
|
|
| |
cfm2 = (cfm3 ± cfm1) |
|
|
| |||
Therefore: |
|
|
|
| ||
T1 | (cfm1) + T2 | (cfm3 | ± cfm1) | |||
|
|
|
|
|
| = T3 |
|
| cfm3 |
|
| ||
|
|
|
|
|
Use this equation to determine cfm1, which is the mini- mum air¯ow across the economizer.
(T3 ± T2) cfm3
cfm1 =
(T1 ± T2)
Fig. 28 Ð Durablade Economizer Barometric Relief
Damper Characteristics
OPTIONAL PARABLADE ECONOMIZER Ð The op- tional PARABLADE economizer hood assembly is pack- aged and shipped in the ®lter section. Damper blades and control boards are installed at the factory and the econo- mizer is shipped in the vertical discharge position.
NOTE: Horizontal discharge
Assembly
1.Determine if ventilation air is required in building. If so, determine the minimum amount to be supplied by each unit and record quantity of ventilation air needed for use in Step 7.
2.Remove ®lter access panel by raising panel and swing- ing panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove ®lter access panel. Remove
3.Assemble
4.On 012 and 014 units, install vertical discharge block- off plate over duct openings. See Fig. 20.
5.Slide economizer into unit and secure with screws. See Fig. 29.
NOTE: Be sure to engage rear economizer ¯ange under tabs in vertical
6.Insert economizer plug into economizer harness. Re- move tape from barometric relief damper. See Fig. 29.
7.If ventilation air is not required, proceed to Step 8. If ventilation air is required, perform the following:
a.Make sure the
b.The 2 potentiometers with slots for adjustment are located on the face of the economizer logic module. Turn the lower potentiometer fully clockwise. The
If cfm1 does not match the desired minimum air¯ow from Step 1,
8.Determine the enthalpy changeover set point from Fig. 30. The enthalpy changeover set point should be set to return the outdoor air damper to the minimum po- sition when enthalpy rises above the set point. The set- tings are A, B, C, and D. Set the enthalpy changeover per the setting in Fig. 30.
9.Replace
10.Fasten hood top and side plate assembly (Fig. 32) to
11.Slide
ECONOMIZER CONTROL
MODULE/DAMPER ACTUATOR
WIRING | ENTHALPY | BAROMETRIC |
HARNESS | SENSOR | RELIEF DAMPER |
Fig. 29 Ð PARABLADE Economizer Installed in Unit
15