MAXIMUM ALLOWABLE
DIFFERENCE (in.)
0.5 | 1.0 | 1.0 |
|
|
|
Fig. 3 Ð Unit Leveling Tolerances
NOTE: Drain plug is shown in
Fig. 4 Ð Condensate Drain Pan
NOTE: Trap should be deep enough to offset maximum unit static difference. A
Fig. 5 Ð External Trap Condensate Drain
Locate mechanical draft system ¯ue assembly at least 48 in. from any opening through which combustion prod- ucts could enter the building, and at least 48 in. from an ad- jacent building or combustible material. When unit is located adjacent to public walkways, ¯ue assembly must be at least 7 ft above grade.
Flue vent discharge must have a minimum horizontal clear- ance of 48 in. from electric and gas meters, gas regulators, and gas relief equipment.
Flue gas can deteriorate building materials. Orient unit so that ¯ue gas will not affect building materials.
Adequate
NOTES:
1. Dimension in ( ) is in millimeters.
2.Hook rigging shackles through holes in base rail as shown in detail ``A.'' Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
3.Weights include base unit without economizer. See Table 1 for economizer weights.
All panels must be in place when rigging.
| MAX |
|
| DIMENSIONS |
|
| ||
UNIT | WEIGHT | ``A'' | ``B'' | ``C'' | ||||
| lb | kg | in. | mm | in. | mm | in. | mm |
48TJD/TJE/TJF008 | 870 | 395 | 87.38 | 2219 | 40.25 | 1022 | 41.31 | 1050 |
48TJD/TJE/TJF009 | 880 | 399 | 87.38 | 2219 | 40.25 | 1022 | 41.31 | 1050 |
48TJD/TJE/TJF012 | 1035 | 469 | 87.38 | 2219 | 40.25 | 1022 | 49.31 | 1253 |
48TJD/TJE014 | 1050 | 476 | 87.38 | 2219 | 40.25 | 1022 | 49.31 | 1253 |
|
|
|
|
|
|
|
|
|
Fig. 6 Ð Rigging Details
4