Carrier 48TJE008-014, 48TJD008-014, 48TJF008-012 installation instructions Airflow

Models: 48TJF008-012 48TJD008-014 48TJE008-014

1 40
Download 40 pages 31.89 Kb
Page 21
Image 21
Manual background

Table 11 Ð Fan Performance, 48TJ008 Ð Horizontal Discharge Units

AIRFLOW

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

0.2

 

0.4

 

0.6

 

0.8

 

0.9

 

1.0

 

1.2

 

1.4

 

1.6

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

2200

499

 

0.50

580

 

0.70

652

 

0.94

717

 

1.17

748

 

1.30

779

 

1.43

839

 

1.78

905

 

2.21

951

 

2.57

2250

507

 

0.53

586

 

0.73

658

 

0.97

722

 

1.22

752

 

1.34

783

 

1.46

843

 

1.81

908

 

2.25

955

 

2.59

2300

513

 

0.55

592

 

0.76

663

 

1.00

727

 

1.26

756

 

1.38

786

 

1.49

846

 

1.84

910

 

2.25

959

 

2.61

2400

528

 

0.60

606

 

0.83

674

 

1.06

738

 

1.34

766

 

1.46

795

 

1.58

853

 

1.88

912

 

2.31

967

 

2.68

2500

542

 

0.66

619

 

0.90

686

 

1.13

748

 

1.41

777

 

1.55

806

 

1.68

859

 

1.94

919

 

2.37

971

 

2.73

2550

550

 

0.69

627

 

0.94

692

 

1.17

754

 

1.45

783

 

1.60

812

 

1.74

864

 

1.99

920

 

2.39

974

 

2.76

2600

557

 

0.72

634

 

0.97

698

 

1.21

759

 

1.49

787

 

1.64

816

 

1.79

868

 

2.04

921

 

2.41

976

 

2.78

2700

573

 

0.79

648

 

1.05

711

 

1.29

770

 

1.58

798

 

1.73

827

 

1.88

878

 

2.16

928

 

2.45

983

 

2.88

2800

588

 

0.86

662

 

1.13

723

 

1.38

782

 

1.66

809

 

1.82

837

 

1.98

889

 

2.29

937

 

2.57

986

 

2.91

2900

604

 

0.94

676

 

1.21

737

 

1.48

794

 

1.76

821

 

1.92

848

 

2.08

900

 

2.41

947

 

2.70

993

 

3.01

3000

620

 

1.02

690

 

1.30

750

 

1.58

806

 

1.86

832

 

2.02

849

 

2.18

910

 

2.52

958

 

2.85

1002

 

3.15

3100

636

 

1.11

704

 

1.39

764

 

1.69

818

 

1.97

844

 

2.13

870

 

2.29

920

 

2.64

968

 

2.99

1012

 

3.30

3200

652

 

1.21

718

 

1.49

778

 

1.80

831

 

2.09

856

 

2.25

882

 

2.40

931

 

2.76

979

 

3.13

1023

 

3.47

3300

668

 

1.31

732

 

1.59

793

 

1.92

844

 

2.21

869

 

2.37

894

 

2.53

942

 

2.89

989

 

3.26

1034

 

3.63

3400

684

 

1.41

747

 

1.70

807

 

2.04

857

 

2.35

882

 

2.51

907

 

2.66

954

 

3.02

1000

 

3.40

1044

 

3.79

3500

701

 

1.53

762

 

1.82

821

 

2.16

871

 

2.48

895

 

2.64

919

 

2.80

966

 

3.15

1011

 

3.55

1054

 

3.94

3600

717

 

1.65

777

 

1.94

835

 

2.29

885

 

2.63

908

 

2.79

932

 

2.95

978

 

3.30

1022

 

3.69

1065

 

4.10

3700

733

 

1.77

792

 

2.07

849

 

2.42

899

 

2.78

922

 

2.95

945

 

3.11

990

 

3.45

1034

 

3.84

1076

 

4.26

3750

742

 

1.84

800

 

2.14

856

 

2.49

907

 

2.86

929

 

3.03

952

 

3.20

997

 

3.54

1040

 

3.93

1082

 

5.27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

Bhp Ð Brake Horsepower Input to Fan

NOTES:

1.Boldface indicates ®eld-supplied drive required. (See Note 4.)

2.Manual backgroundManual background indicates alternate drive required.

3.Manual backgroundManual background indicates ®eld-supplied motor and drive required.

4.Standard drive range is 590 to 840 rpm. Alternate drive range is 685 to 935 rpm. All other rpms require a ®eld-supplied drive.

5.Values include losses for ®lters, unit casing, and wet coils.

6.Maximum continuous bhp is 2.4. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the rat- ings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

7.Use of a ®eld-supplied motor may affect wire sizing. Contact your Carrier representative to verify.

8.Interpolation is permissible. Do not extrapolate.

Table 12 Ð Fan Performance, 48TJ009 Ð Horizontal Discharge Units

AIRFLOW

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

0.2

 

0.4

 

0.6

 

0.8

 

0.9

 

1.0

 

1.2

 

1.4

 

1.6

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

2550

550

 

0.69

627

 

0.94

692

 

1.17

754

 

1.45

783

 

1.60

812

 

1.74

864

 

1.99

920

 

2.39

974

 

2.76

2600

557

 

0.72

634

 

0.97

698

 

1.21

759

 

1.49

787

 

1.64

816

 

1.79

868

 

2.04

921

 

2.41

976

 

2.78

2700

573

 

0.79

648

 

1.05

711

 

1.29

770

 

1.58

798

 

1.73

827

 

1.88

878

 

2.16

928

 

2.45

983

 

2.88

2800

588

 

0.86

662

 

1.13

723

 

1.38

782

 

1.66

809

 

1.82

837

 

1.98

889

 

2.29

937

 

2.57

986

 

2.91

2900

604

 

0.94

676

 

1.21

737

 

1.48

794

 

1.76

821

 

1.92

848

 

2.08

900

 

2.41

947

 

2.70

993

 

3.01

3000

620

 

1.02

690

 

1.30

750

 

1.58

806

 

1.86

832

 

2.02

849

 

2.18

910

 

2.52

958

 

2.85

1002

 

3.15

3100

636

 

1.11

704

 

1.39

764

 

1.69

818

 

1.97

844

 

2.13

870

 

2.29

920

 

2.64

968

 

2.99

1012

 

3.30

3200

652

 

1.21

718

 

1.49

778

 

1.80

831

 

2.09

856

 

2.25

882

 

2.40

931

 

2.76

979

 

3.13

1023

 

3.47

3300

668

 

1.31

732

 

1.59

793

 

1.92

844

 

2.21

869

 

2.37

894

 

2.53

942

 

2.89

989

 

3.26

1034

 

3.63

3400

684

 

1.41

747

 

1.70

807

 

2.04

857

 

2.35

882

 

2.51

907

 

2.66

954

 

3.02

1000

 

3.40

1044

 

3.79

3500

701

 

1.53

762

 

1.82

821

 

2.16

871

 

2.48

895

 

2.64

919

 

2.80

966

 

3.15

1011

 

3.55

1054

 

3.94

3600

717

 

1.65

777

 

1.94

835

 

2.29

885

 

2.63

908

 

2.79

932

 

2.95

978

 

3.30

1022

 

3.69

1065

 

4.10

3700

733

 

1.77

792

 

2.07

849

 

2.42

899

 

2.78

922

 

2.95

945

 

3.11

990

 

3.45

1034

 

3.84

1076

 

4.26

3750

742

 

1.84

800

 

2.14

856

 

2.49

907

 

2.86

929

 

3.03

952

 

3.20

997

 

3.54

1040

 

3.93

1082

 

5.27

3800

750

 

1.90

807

 

2.21

863

 

2.56

914

 

2.93

936

 

3.11

958

 

3.28

1003

 

3.62

1045

 

4.01

1087

 

4.43

3900

767

 

2.04

822

 

2.35

877

 

2.71

928

 

3.09

950

 

3.27

972

 

3.45

1015

 

3.80

1057

 

4.18

1098

 

4.60

4000

783

 

2.18

838

 

2.50

891

 

2.86

942

 

3.26

964

 

3.45

986

 

3.63

1028

 

3.99

1070

 

4.36

1110

 

4.78

4100

800

 

2.34

854

 

2.66

905

 

3.02

956

 

2.43

978

 

3.62

1000

 

3.81

1042

 

4.18

1082

 

4.56

1122

 

4.97

4200

817

 

2.49

869

 

2.82

920

 

3.19

970

 

3.60

992

 

3.80

1015

 

4.00

1055

 

4.38

1095

 

4.76

1134

 

5.16

4250

826

 

2.58

877

 

2.91

928

 

3.28

977

 

3.69

999

 

3.90

1022

 

4.10

1062

 

4.49

1102

 

4.87

1140

 

5.27

4300

834

 

2.66

885

 

3.00

935

 

3.37

984

 

3.78

1006

 

3.99

1029

 

4.20

1069

 

4.59

1108

 

4.98

1147

 

5.38

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

Bhp Ð Brake Horsepower Input to Fan

NOTES:

1.Boldface indicates ®eld-supplied drive required. (See Note 3.)

2.Manual backgroundManual background indicates ®eld-supplied motor and drive required.

3.Standard drive range is 685 to 935 rpm. All other rpms require a ®eld-supplied drive.

4.Values include losses for ®lters, unit casing, and wet coils.

5.Maximum continuous bhp is 2.4. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the rat- ings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

6.Use of a ®eld-supplied motor may affect wire sizing. Contact your Carrier representative to verify.

7.Interpolation is permissible. Do not extrapolate.

21

Page 21