PREMIERLINK™ CONTROLLER INPUTS AND OUT- PUTS — When PremierLink controllers are factory mounted with water source heat pump equipment to implement a CCN system installation, the inputs and outputs are shown in Table 3.
CONNECT POWER — The Aquazone™ system control panel requires an uninterrupted
inside the enclosure. Supply power to the Aquazone system control panel through the convenience outlet in the bottom left hand corner of the Aquazone system control panel. Do not apply power until all connections have been made and voltage supply has been verified. Ground in accordance with NEC and local electrical codes. Connect the dedicated ground wire to the position in relationship to the main supply line and use shield cable to protect from any electrical interference.
CONTROL WIRING — Low voltage wiring for the Aqua- zone system control panel is shown in Fig. 8.
Table 3 — PremierLink Controller Inputs and Outputs
| INPUTS | POWER | TERMINAL(S) |
| SPACE TEMPERATURE (SPT) | AI (10 K Thermistor) | |
| SET POINT ADJUSTMENT (STO) | AI (10 K Thermistor) | |
| SUPPLY AIR TEMPERATURE (SAT) | AI (10 K Thermistor) | |
| LEAVING WATER TEMPERATURE | AI (10 K Thermistor) | |
| IAQ SENSOR (IAQI) | ||
| REMOTE TIME CLOCK (RMTOCC) | DI (24 vac) | |
| COMPRESSOR LOCKOUT (CMPSAFE) | DI (24 vac) | |
| FIRE SHUTDOWN (FSD) | DI (24 vac) | |
| SUPPLY FAN STATUS (SFS) | DI (24 vac) | |
| NOT USED | — | — |
| OUTPUTS | POWER | TERMINALS |
| FAN (SF) | DO Relay (24 vac, 1A) | |
| COOL STAGE 1 (CMP1) | DO Relay (24 vac, 1A) | |
| COOL STAGE 2 (CMP2) | DO Relay (24 vac, 1A) | |
| HEAT STAGE 1 (HS1) | DO Relay (24 vac, 1A) | |
| HEAT STAGE 2 (HS2) | DO Relay (24 vac, 1A) | |
| HEAT 3/EXHAUST/REVERSING VALVE (HS3/EXH/RVS) | DO Relay (24 vac, 1A) | |
| LEGEND |
|
|
AI | — Analog Input |
|
|
DI | — Digital Input |
|
|
DO — Digital Output
11