CONFIGURATION

The Aquazone™ System Control Panel contains a Comfort Controller 6400 programmed using the standard algorithms and enhanced by BEST++™ custom programming. The BEST++ Templates for some of the programs have been removed to prevent field alterations. For other programs, the templates are included to allow for jobsite customization. For basic information about the algorithms please refer to the Comfort Controller Overview and Configuration manual (808-891). Default configurations are listed later in this section.

Hardware Points — The hardware points are shown in Table 11 and 12.

Table 11 — Hardware Points 1 to 32 (HWP01-32)

DESCRIPTION

VALUE

NAME

Loop Water Flow

Yes

FLOW

System Supply Water Temp

60.3 dF

SSWT

System Return Water Temp

51.0 dF

SRWT

System Diff. Pressure

0.00 PSIG

SDP

Remote Occupancy Mode

Off

RMTOCC

System

Enable

ALLSYS

Override Input Zone 1

On

OVRIZ1

Override Input Zone 2

On

OVRIZ2

Pump Number 1 Speed

100.0%

PUMP1

Pump Number 2 Speed

0.0%

PUMP2

Cooling Tower 1 Level

0.0%

CTL1

Cooling Tower 2 Level

0.0%

CTL2

Boiler 1 Level

83.2%

BLRL1

Boiler 2 Level

0.0%

BLRL2

System for Zone 1

Enable

SYSZ1

System for Zone 2

Enable

SYSZ2

Override Input Zone 3

Off

OVRIZ3

Override Input Zone 4

Off

OVRIZ4

Override Input Zone 5

Off

OVRIZ5

Override Input Zone 6

Off

OVRIZ6

Override Input Zone 7

Off

OVRIZ7

Override Input Zone 8

Off

OVRIZ8

Override Input Zone 9

Off

OVRIZ9

Override Input Zone 10

Off

OVRIZ10

System for Zone 3

Disable

SYSZ3

System for Zone 4

Disable

SYSZ4

System for Zone 5

Disable

SYSZ5

System for Zone 6

Disable

SYSZ6

System for Zone 7

Disable

SYSZ7

System for Zone 8

Disable

SYSZ8

System for Zone 9

Disable

SYSZ9

System for Zone 10

Disable

SYSZ10

Table 12 — Hardware Points 33 to 64 (HWP33-64)

DESCRIPTION

VALUE

NAME

Override Input Zone 11

Off

OVRIZ11

Override Input Zone 12

Off

OVRIZ12

Override Input Zone 13

Off

OVRIZ13

Override Input Zone 14

Off

OVRIZ14

Override Input Zone 15

Off

OVRIZ15

Override Input Zone 16

Off

OVRIZ16

Override Input Zone 17

Off

OVRIZ17

Override Input Zone 18

Off

OVRIZ18

System for Zone 11

Disable

SYSZ11

System for Zone 12

Disable

SYSZ12

System for Zone 13

Disable

SYSZ13

System for Zone 14

Disable

SYSZ14

System for Zone 15

Disable

SYSZ15

System for Zone 16

Disable

SYSZ16

System for Zone 17

Disable

SYSZ17

System for Zone 18

Disable

SYSZ18

LOOP WATER FLOW SWITCH — This discrete input is used to provide a signal that one of the loop water pumps is on. If both pumps have been commanded to run and no water flow is detected, then the system water source heat pumps will run in the fan only mode for DDC (Direct Digital Control) coordinated heat pump controllers, while the system relays for thermostat systems will be turned off.

Loop Water Flow Switch:

 

Display Units

Discrete ASCII

Default Value

No

Display Range

Yes/No

Network Access

Read/Write

SYSTEM SUPPLY WATER TEMPERATURE — The sys- tem supply water temperature is the temperature of the water being pumped to the system of water source heat pumps. The temperature is measured by a 10K Thermistor (MCI). This output and sensor is required for proper function of the loop and heat pumps.

System Supply Water Temperature:

Display Units

degrees F (degrees C)

Default Value

–40.0

Display Range

–40.0-245.0

Network Access

Read/Write

SYSTEM RETURN WATER TEMPERATURE — The sys- tem return water temperature is the temperature of the water returning from the system of water source heat pumps. This temperature measured by a 10K Thermistor (MCI). This output and sensor is provided for informational purpose and indicates the average load caused by the normal operation of the heat pumps.

System Return Water Temperature:

Display Units

degrees F (degrees C)

Default Value

–40.0

Display Range

–40.0-245.0

Network Access

Read/Write

SYSTEM WATER PRESSURE — This sensor is used to measure the pressure of the supply water to the system of water source heat pumps. This sensor should be located 2/3 of the way down the supply water distribution piping or in a location that will provide a good reference of the supply water pressure. This sensor is used to control the speed of variable frequency drives pumping water to the water source heat pumps. Each water source heat pump may be equipped with a two position isolation valve that may be closed when the compressors are not energized in order to reduce the quantity of water being pumped through the system.

System Water Pressure:

 

Display Units

in. wg

Default Value

0.0

Display Range

0.0-5.0

Network Access

Read/Write

21

Page 21
Image 21
Carrier 50RLP Configuration, Hardware Points 1 to 32 HWP01-32, Hardware Points 33 to 64 HWP33-64, Description Value Name

50RLP specifications

The Carrier 50RLP is a well-regarded air conditioning unit that combines efficiency, durability, and innovative technology to provide optimal cooling solutions for both residential and commercial applications. This model is part of Carrier's extensive lineup designed to meet various climate control needs.

One of the standout features of the Carrier 50RLP is its high energy efficiency rating. Equipped with a scroll compressor, the system operates efficiently, reducing energy consumption significantly. This not only lowers utility bills for the user but also contributes to a smaller carbon footprint, making it an environmentally friendly choice. The unit adheres to stringent energy standards, often exceeding the minimum requirements, which is especially advantageous in regions with strict energy codes.

The Carrier 50RLP also boasts advanced refrigerant technology. Utilizing R-410A refrigerant, the unit is designed to minimize ozone depletion potential. R-410A is known for its effectiveness in heat exchange as well as its stability, thus ensuring reliable performance over the unit's lifespan. Additionally, the option for variable refrigerant flow technology in some variants of the 50RLP allows for precise temperature control, making it adaptable to varying cooling needs.

Durability is another hallmark of the Carrier 50RLP. The unit features a robust construction with weatherproof materials that withstand harsh environmental conditions. This resilience is crucial for outdoor installations and contributes to a longer lifespan. Carrier also incorporates innovative sound reduction technologies, allowing the unit to operate quietly, making it suitable for both residential and commercial settings where noise levels are a concern.

Furthermore, the Carrier 50RLP is equipped with advanced controls. The inclusion of smart thermostat capabilities enables users to manage and schedule cooling efficiently, optimizing energy usage based on occupancy or time of day. These controls can often be integrated with home automation systems, enhancing user convenience.

In summary, the Carrier 50RLP air conditioning unit brings together high efficiency, innovative refrigerant technology, robust durability, and advanced smart controls. Its design not only meets the cooling demands of various spaces but also promotes energy savings and environmental sustainability. Ideal for both residential and commercial applications, the Carrier 50RLP stands out as a reliable choice for maintaining comfortable indoor environments. Whether for new installations or replacements, this model is a testament to Carrier's commitment to quality and innovation in HVAC technology.