Carrier 50RLP Components, Aquazone System Control Panel Hardware, Model Number Nomenclature

Models: 50RLP

1 28
Download 28 pages 1.7 Kb
Page 2
Image 2
COMPONENTS

The Aquazone™ System Control Panel is a single packaged system control panel for use with Aquazone water source heat pumps (WSHPs) in stand-alone or direct digital control applications using the Carrier Comfort Network (CCN). The Aquazone system control panel controls and monitors the operation of the water source heat pumps, the ancillary heat rejection, the heat addition, and the system pumps to coordi- nate entire system operation. The Aquazone System Control Panel is used with the following units: 50HQL, KQA, KQD, RDS, RHC, RHR, RHS, RTG, RVC, RVR, RVS, RWS, VQA, VQD.

The Aquazone system control panel includes a pre- programmed 6400 main logic comfort controller as the central processing unit. The Aquazone system control panel is compat- ible for use in boiler/tower (water loop) or geothermal (ground loop, ground water) water source heat pump arrangements.

Other system hardware components are specified in the 50RLP model nomenclature. Components can be added to cus- tomize the Aquazone System Control Panel for the specific type of functionality desired, including staged heat rejection and addition, dual or variable speed pump operation, and stand- alone or CCN installations. See Fig. 1.

Aquazone System Control Panel Functional- ity — Functionality includes the ability to control up to two water-circulating pumps and monitor water temperature to initiate up to eight stages of cooling tower and/or boiler opera- tion. The system control panel has the capability to work with variable speed pumping arrangements for maximum energy efficiency. In addition, the panel provides system control for both stand-alone and DDC water source heat pump systems (units installed with a factory-mounted PremierLink™ CCN controller).

Stand-Alone Systems — In a stand-alone type of con- trol strategy, non-communicating Aquazone water source heat pump thermostats are utilized to initiate the operation of individual water source heat pump equipment for each zone. The Aquazone System Control Panel can be ordered with the appropriate hardware to accommodate and initiate scheduled control of either 10 or 18 zones of WSHP units in stand-alone operation. See Fig. 2.

CCN Systems Using PremierLink Controls — To implement a direct digital control type of water source heat pump system strategy, individual WSHP units are ordered with a factory-installed PremierLink controller. The Aquazone sys- tem control panel has been pre-programmed to work specifi- cally with the PremierLink controller to transfer and control all modes of cooling/heating operation, transmit unit number, zone temperature, zone temperature set points, discharge air temperature, fan status, stages of heating, stages of cooling, leaving water temperature, and alarm status information. See Fig. 3.

COMPONENTS

Aquazone System Control Panel Hardware —

The 50RLP Aquazone System Control Panel package consists of the following hardware. See Fig. 4.

ENCLOSURE — The Aquazone system control panel enclo- sure is constructed of perforated 16-gage steel and finished in a gray powder-coated finish. The panel has a height of 42 in., a width of 30 in. and a depth of 7 inches.

PROCESSOR — The central processing units for the Aqua- zone system control panel are Carrier 6400 Comfort Control- lers. The Comfort Controller provides general purpose HVAC control and monitoring capability in a stand-alone or network environment using closed-loop, direct digital control. The 6400 Comfort Controller has been pre-programmed to work in either stand-alone or CCN water source heat pump system installa- tions. Specifications for the 6400 Comfort Controller may be found in the Comfort Controller literature.

PUMP CONTROL RELAYS — For both stand-alone and CCN systems (based on the type of pumping operation required) the Aquazone system control panel can be ordered with a combination of multi-voltage control relays to provide start/stop or lead/lag operation for single or dual pumps. The combination desired is specified in the 50RLP model nomen- clature in digit 8. See Fig. 1.

50RLP 0 0 0 0

Unit

50RLP – Aquazone System Control Panel

System Heat Rejection

02-Stage Card (2 Stages of Cooling Tower Operation)

14-Stage Card (4 Stages of Cooling Tower Operation)

22- and 4-Stage Cards (6 Stages of Cooling Tower Operation)

3Two 4-Stage Cards (8 Stages of Cooling Tower Operation)

4No Card, Variable Speed Cooling Tower Operation

WSHP Zone Operation

010 Relays, Control 10 Zones for Stand-Alone WSHP Units*

118 Relays, Control 18 Zones for Stand-Alone WSHP Units*

2No Relays, Carrier Comfort Network (CCN) System†

System Pumping Operation

0Both Relays, Start/Stop or Lead/Lag Operation for Single or Dual Pumps

1No Relays, Variable Frequency Pump Operation**

System Heat Addition

02-Stage Card (2 Stages of Boiler Operation)

14-Stage Card (4 Stages of Boiler Operation)

22 and 4-Stage Cards (6 Stages of Boiler Operation)

3Two 4-Stage Cards (8 Stages of Boiler Operation)

4No Card, Modulating Valve Operation for Steam or Hot Water

*Option is utilized with Aquazone Thermostat for each WSHP unit.

†Option is utilized with PremierLink DDC control option on individual WSHP units. **Accepts signals from a variable frequency device.

Fig. 1 — Model Number Nomenclature

2

Page 2
Image 2
Carrier 50RLP installation instructions Components, Aquazone System Control Panel Hardware, Model Number Nomenclature