The Aquazone™ System Control Panel is a single packaged system control panel for use with Aquazone water source heat pumps (WSHPs) in
The Aquazone system control panel includes a pre- programmed 6400 main logic comfort controller as the central processing unit. The Aquazone system control panel is compat- ible for use in boiler/tower (water loop) or geothermal (ground loop, ground water) water source heat pump arrangements.
Other system hardware components are specified in the 50RLP model nomenclature. Components can be added to cus- tomize the Aquazone System Control Panel for the specific type of functionality desired, including staged heat rejection and addition, dual or variable speed pump operation, and stand- alone or CCN installations. See Fig. 1.
Aquazone System Control Panel Functional- ity — Functionality includes the ability to control up to two
CCN Systems Using PremierLink Controls — To implement a direct digital control type of water source heat pump system strategy, individual WSHP units are ordered with a
COMPONENTS
Aquazone System Control Panel Hardware —
The 50RLP Aquazone System Control Panel package consists of the following hardware. See Fig. 4.
ENCLOSURE — The Aquazone system control panel enclo- sure is constructed of perforated
PROCESSOR — The central processing units for the Aqua- zone system control panel are Carrier 6400 Comfort Control- lers. The Comfort Controller provides general purpose HVAC control and monitoring capability in a
PUMP CONTROL RELAYS — For both
50RLP 0 0 0 0
Unit
50RLP – Aquazone System Control Panel
System Heat Rejection
0–
1–
2– 2- and
3– Two
4– No Card, Variable Speed Cooling Tower Operation
WSHP Zone Operation
0– 10 Relays, Control 10 Zones for
1– 18 Relays, Control 18 Zones for
2– No Relays, Carrier Comfort Network (CCN) System†
System Pumping Operation
0– Both Relays, Start/Stop or Lead/Lag Operation for Single or Dual Pumps
1– No Relays, Variable Frequency Pump Operation**
System Heat Addition
0–
1–
2– 2 and
3– Two
4– No Card, Modulating Valve Operation for Steam or Hot Water
*Option is utilized with Aquazone Thermostat for each WSHP unit.
†Option is utilized with PremierLink DDC control option on individual WSHP units. **Accepts signals from a variable frequency device.
Fig. 1 — Model Number Nomenclature
2