OCCUPIED FROM — This field is used to configure the hour and minute, in military time, that the mode for the PremierLink™ controller will switch to occupied.
Occupied From: Units | Hours:Minutes |
Range | 00:00 to 24:00 |
| (Minutes 00 to 59) |
Default Value | 00:00 |
OCCUPIED TO — This field is used to configure the hour and minute, in military time, that the mode for the PremierLink controller switches from occupied to unoccupied.
Occupied To: | Units |
| Hours:Minutes | ||
| Range |
| 00:00 to 24:00 |
| |
|
|
| (Minutes 00 to 59) | ||
| Default Value | 24:00 |
|
| |
Table 21 — Occupancy Schedule (OCCPC01) | |||||
|
|
|
|
| |
DESCRIPTION |
| VALUE |
| NAME | |
Time Schedule |
|
|
|
|
|
Manual Override Hours |
| 0 hours |
| Ovrd | |
Period 1: Day of Week |
| 00000000 |
| DOW1 | |
Period 1: Occupied from |
| 00:00 |
| Occ1 | |
Period 1: Occupied to |
| 24:00 |
| UnOcc1 | |
Period 2: Day of Week |
| 00000000 |
| DOW2 | |
Period 2: Occupied from |
| 00:00 |
| Occ2 | |
Period 2: Occupied to |
| 24:00 |
| UnOcc2 | |
Period 3: Day of Week |
| 00000000 |
| DOW3 | |
Period 3: Occupied from |
| 00:00 |
| Occ3 | |
Period 3: Occupied to |
| 24:00 |
| UnOcc3 | |
Period 4: Day of Week |
| 00000000 |
| DOW4 | |
Period 4: Occupied from |
| 00:00 |
| Occ4 | |
Period 4: Occupied to |
| 24:00 |
| UnOcc4 | |
Period 5: Day of Week |
| 00000000 |
| DOW5 | |
Period 5: Occupied from |
| 00:00 |
| Occ5 | |
Period 5: Occupied to |
| 24:00 |
| UnOcc5 | |
Period 6: Day of Week |
| 00000000 |
| DOW6 | |
Period 6: Occupied from |
| 00:00 |
| Occ6 | |
Period 6: Occupied to |
| 24:00 |
| UnOcc6 | |
Period 7: Day of Week |
| 00000000 |
| DOW7 | |
Period 7: Occupied from |
| 00:00 |
| Occ7 | |
Period 7: Occupied to |
| 24:00 |
| UnOcc7 | |
Period 8: Day of Week |
| 00000000 |
| DOW8 | |
Period 8: Occupied from |
| 00:00 |
| Occ8 | |
Period 8: Occupied to |
| 24:00 |
| UnOcc8 | |
Push Button Override |
| LATCHI00 |
| Name* | |
Thermostat Override | TEMP_I00 |
| Name* | ||
Time Delay |
|
| 5 min |
| Value* |
Timed Override Duration |
| 5 min |
| Value* | |
Power on Delay |
|
| 0 sec |
| PowerUp |
*User configured.
Network Time Schedule — The network time schedule allows the occupancy schedule in another device on the CCN to control the Aquazone™ system control panel’s occupancy state.
Each time the occupancy schedule on the controlling device changes to occupied, the controlling device broadcasts an occupancy flag over the CCN. To receive an occupancy flag, a network time created. Up to 18 network time schedules are configured. The schedules are sequentially named OCCPC65E to OCCPC82E, however Service Tool or Building Supervisor software can be used to modify the names up to OCCPC99E.
Holiday Schedules — A Holiday schedule allows the user the capability to specify days of the year (holidays) on which the Aquazone system control panel will follow the holiday time schedule instead of the normal time schedule for that day. Holiday time schedules are normally used to program a weekday in unoccupied mode for the entire day since the building will be empty during a holiday.
There are 16 different holiday schedules that can be created. Holiday schedules can also last more than one day, as long as the days are consecutive.
Holiday schedules must be configured on the time and date broadcaster element on the CCN. If the Comfort Controller on the Aquazone system control panel is the broadcaster, it will send holiday status to all other system elements on the CCN. If the Comfort Controller is not the broadcaster, do not configure the holiday schedules for it, as they will not be used.
To configure a holiday schedule, enter a “1” in the Holiday column of the Day of Week point of the Occupancy schedule.