Carrier 50RLP installation instructions Occupancy Schedule OCCPC01

Models: 50RLP

1 28
Download 28 pages 1.7 Kb
Page 27
Image 27

OCCUPIED FROM — This field is used to configure the hour and minute, in military time, that the mode for the PremierLink™ controller will switch to occupied.

Occupied From: Units

Hours:Minutes

Range

00:00 to 24:00

 

(Minutes 00 to 59)

Default Value

00:00

OCCUPIED TO — This field is used to configure the hour and minute, in military time, that the mode for the PremierLink controller switches from occupied to unoccupied.

Occupied To:

Units

 

Hours:Minutes

 

Range

 

00:00 to 24:00

 

 

 

 

(Minutes 00 to 59)

 

Default Value

24:00

 

 

Table 21 — Occupancy Schedule (OCCPC01)

 

 

 

 

 

DESCRIPTION

 

VALUE

 

NAME

Time Schedule

 

 

 

 

 

Manual Override Hours

 

0 hours

 

Ovrd

Period 1: Day of Week

 

00000000

 

DOW1

Period 1: Occupied from

 

00:00

 

Occ1

Period 1: Occupied to

 

24:00

 

UnOcc1

Period 2: Day of Week

 

00000000

 

DOW2

Period 2: Occupied from

 

00:00

 

Occ2

Period 2: Occupied to

 

24:00

 

UnOcc2

Period 3: Day of Week

 

00000000

 

DOW3

Period 3: Occupied from

 

00:00

 

Occ3

Period 3: Occupied to

 

24:00

 

UnOcc3

Period 4: Day of Week

 

00000000

 

DOW4

Period 4: Occupied from

 

00:00

 

Occ4

Period 4: Occupied to

 

24:00

 

UnOcc4

Period 5: Day of Week

 

00000000

 

DOW5

Period 5: Occupied from

 

00:00

 

Occ5

Period 5: Occupied to

 

24:00

 

UnOcc5

Period 6: Day of Week

 

00000000

 

DOW6

Period 6: Occupied from

 

00:00

 

Occ6

Period 6: Occupied to

 

24:00

 

UnOcc6

Period 7: Day of Week

 

00000000

 

DOW7

Period 7: Occupied from

 

00:00

 

Occ7

Period 7: Occupied to

 

24:00

 

UnOcc7

Period 8: Day of Week

 

00000000

 

DOW8

Period 8: Occupied from

 

00:00

 

Occ8

Period 8: Occupied to

 

24:00

 

UnOcc8

Push Button Override

 

LATCHI00

 

Name*

Thermostat Override

TEMP_I00

 

Name*

Time Delay

 

 

5 min

 

Value*

Timed Override Duration

 

5 min

 

Value*

Power on Delay

 

 

0 sec

 

PowerUp

*User configured.

Network Time Schedule — The network time schedule allows the occupancy schedule in another device on the CCN to control the Aquazone™ system control panel’s occupancy state.

Each time the occupancy schedule on the controlling device changes to occupied, the controlling device broadcasts an occupancy flag over the CCN. To receive an occupancy flag, a network time created. Up to 18 network time schedules are configured. The schedules are sequentially named OCCPC65E to OCCPC82E, however Service Tool or Building Supervisor software can be used to modify the names up to OCCPC99E.

Holiday Schedules — A Holiday schedule allows the user the capability to specify days of the year (holidays) on which the Aquazone system control panel will follow the holiday time schedule instead of the normal time schedule for that day. Holiday time schedules are normally used to program a weekday in unoccupied mode for the entire day since the building will be empty during a holiday.

There are 16 different holiday schedules that can be created. Holiday schedules can also last more than one day, as long as the days are consecutive.

Holiday schedules must be configured on the time and date broadcaster element on the CCN. If the Comfort Controller on the Aquazone system control panel is the broadcaster, it will send holiday status to all other system elements on the CCN. If the Comfort Controller is not the broadcaster, do not configure the holiday schedules for it, as they will not be used.

To configure a holiday schedule, enter a “1” in the Holiday column of the Day of Week point of the Occupancy schedule.

27

Page 27
Image 27
Carrier 50RLP installation instructions Occupancy Schedule OCCPC01