![](/images/new-backgrounds/1078607/7860783x1.webp)
1
6
TO CHILLED WATER PUMP TO CONDENSER WATER PUMP TO COOLING TOWER FAN
9
TO
COOLING
TOWER
MAIN COMPRESSOR
MOTOR POWER
1 | 1 | 1 |
|
|
8
2
9
| 3 |
FROM | SEE NOTE 4 |
COOLING |
|
TOWER | FROM |
| |
| LOAD |
| TO |
| LOAD |
5 | DRAIN |
| |
| 4 |
a23-1594
LEGEND
1— Disconnect (Fused on VFD only) NOT by Carrier
2— Unit Mounted VFD/Control Center
3— Pressure Gages
4— Chilled Water Pump
5— Condenser Water Pump
6— Chilled Water Pump Starter
7— Condensing Water Pump Starter
8— Cooling Tower Fan Starter
9— Vents
Piping
Control Wiring
Power Wiring
IMPORTANT: Wiring and piping shown are for general
NOTES:
1.All wiring must comply with applicable codes.
2.Refer to Carrier System Design Manual for details regarding piping techniques.
3.Wiring not shown for optional devices such as:
•remote
•remote alarm
•optional safety device
•4 to 20 mA (1 to 5 VDC) resets
•optional remote sensors
•kW output
•head pressure reference
4.Service clearance under the chiller can be enhanced if the grout is not extended along the entire length of the heat exchangers.
5.Carrier does not recommend
6.
7.Relief valves on the cooler and condenser must be vented to the outdoors as discharging refrigerant in closed spaces may displace oxygen and cause asphyxiation. All
Dual pressure relief valves are mounted on the
The flow area of discharge piping routed from more than one relief valve, or more than one heat exchanger, must be greater than the sum of the outlet areas of all relief valves that are expected to dis- charge simultaneously. All relief valves within a machinery room that are exposed to refrigerant may discharge simultaneously in the event of a fire. Discharge piping should lead to the point of final release as directly as possible with consideration of pressure drop in all sections downstream of the relief valves.
8. Service access should be provided per standards ANSI/ASHRAE 15 and ANSI/NFPA 70 (NEC) and local safety codes. Unobstructed space adequate for inspection, servicing and rigging of all major components of the chiller is required. Shaded service areas are shown on the certified machine assembly drawing plan view and front view. See machine assembly component disassembly drawing for component removal. Space for rigging equipment and compres- sor removal is not shown.
9.The installation of chilled water and cooling tower water strainers should be considered to prevent debris from collecting in the water- boxes and degrading performance.
10.Flexible conduit should be used for the last few feet to the control center for vibration isolation of power wiring and control wiring.
Fig. 50 — 23XRV with Unit-Mounted VFD/Control Center
42