Carrier HFC-134A installation instructions A23-1555, A23-1556

Models: HFC-134A

1 52
Download 52 pages 7.22 Kb
Page 7
Image 7

a23-1555

Fig. 7 — Machine Electrical Data Nameplate

HEAT EXHANGER

COMPRESSOR

MAXIMUM WEIGHT

VESSEL

DIM.

CHAIN LENGTH

DIM.

DIM.

CODE

FRAME SIZE*

(lb)

LENGTH

“A”

“B”

“C”

“D”

“E”

“F”

30-32

 

19,187

12

6-10

13- 5

13-0

12- 5

3-11

3- 8

35-37

 

20,589

14

7- 8

13-10

13-5

12-10

3-11

3- 8

40-42

R

23,928

12

6-10

13- 6

12-8

12- 3

4- 1

3-11

45-47

25,167

14

7- 8

13-11

13-2

12- 8

4- 1

3-11

 

50-52

 

26,950

12

6-10

13-10

12-7

12- 9

4- 0

4- 4

55-57

 

28,479

14

7- 8

14- 4

13-1

13- 1

4- 0

4- 4

*The 11th character of the chiller model number indicates the frame size of the compressor.

CHAIN “B”

CHAIN “D”

(SEE NOTE #2)

(SEE NOTE #2)

CHAIN “C”

(SEE NOTE #2)

15´-0´´

MIN. HEIGHT ABOVE FLOOR

“E”

“A”

“F”

a23-1556

MACHINE RIGGING GUIDE

NOTES:

1.Each chain must be capable of supporting the entire weight of the machine. See chart for maxi- mum weights.

2.Chain lengths shown are typical for 15lifting height. Some minor adjustments may be required.

Fig. 8 — Machine Rigging Guide (Cooler Size 30 Through 57)

7

Page 7
Image 7
Carrier HFC-134A installation instructions A23-1555, A23-1556