INSTALLATION START-UP REQUEST CHECKLIST

Machine Model Number: 23XRV Serial Number:

To:

Attn.:

Date

Project Name

Carrier Job Number

The following information provides the status of the chiller installation. Send a copy of this checklist to the local Carrier Service office after it has been completed and signed-off by the Purchaser and Job Site Supervisor.

YES/NO

DATE TO BE

(N/A)

COMPLETED

1.The machine is level within 1/2 in. end to end.

2.The machine components are installed and connected in accordance with the installation instructions.

3.The isolation package and grouting (if necessary) are installed.

4.The relief valves are piped to the atmosphere.

5.All piping is installed and supported. Direction of flow

is indicated in accordance with the installation instructions and job prints.

a.Chilled water piping

b.Condenser water piping

c.Waterbox drain piping

d.Pumpout unit condenser piping (if installed)

e.Other

6.Gages are installed as called for on the job prints required to establish design flow for the cooler and condenser.

a.Water pressure gages IN and OUT

b.Water temperature gages IN and OUT

7.The machine’s control center wiring is complete. The wiring is installed per installation instructions and certified prints.

a.Power wiring to VFD circuit breaker. (If chiller was disassembled during installation, motor leads must not be taped until the Carrier technician megger tests

the motor.)

b.Carrier controls can independently energize water pumps and tower fan.

c.Line side voltage is within ±10% of chiller nameplate voltage.

d.Other

COMMENTS:

 

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

2

Catalog No. 532-309

Printed in U.S.A.

Form 23XRV-1SI

Pg CL-1

309 6-06

Replaces: New

Tab

5e

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 51
Image 51
Carrier HFC-134A installation instructions Installation START-UP Request Checklist

HFC-134A specifications

Carrier HFC-134A, also known as tetrafluoroethane, is a hydrofluorocarbon (HFC) refrigerant widely used in a variety of cooling and heating applications. It is recognized for its role in refrigeration and air conditioning systems, making it a crucial component in many modern HVAC units. One of the key features of HFC-134A is its zero ozone depletion potential, which makes it an environmentally friendly alternative to older refrigerants like CFCs and HCFCs.

The characteristics of HFC-134A include its stability, non-corrosiveness, and effectiveness at low temperatures. These properties allow it to perform efficiently in both residential and commercial refrigeration systems. The refrigerant operates within a temperature range that is ideal for many applications, including food preservation and air conditioning. HFC-134A's thermodynamic properties enable it to absorb and release heat effectively, making it suitable for both vapor-compression and absorption refrigeration cycles.

From a technological perspective, the use of HFC-134A aligned with the transition to more sustainable refrigerants. As global environmental regulations have tightened, manufacturers have shifted towards refrigerants with lower global warming potential (GWP). HFC-134A has a GWP of approximately 1,430, which is lower than many of its predecessors but still higher than some newer alternatives. This aspect drives ongoing research and development in the industry, aiming to create even more environmentally sound refrigerants.

Carrier HFC-134A is compatible with various lubricants and can be integrated into systems designed for other refrigerants with minimal modifications. This flexibility allows for a smoother transition within existing installations as businesses and homeowners upgrade their HVAC systems to comply with environmental regulations.

In summary, Carrier HFC-134A plays a significant role in modern refrigeration and air conditioning technology. Its main features, including zero ozone depletion potential, stability, and efficiency, contribute to its widespread use in various applications. As the industry continues to evolve, the focus on reducing the environmental impact of refrigerants will undoubtedly influence the future direction of HFC-134A usage and the development of new alternatives.