3.6.4 Condenser Motor Removal

To remove condenser fan motor, do the following: a. Perform steps outlined in Section 3.6.2.

b. Remove (3) 13MM bolts (See Figure 3-31).

c. Remove (3) Grommets. Inspect, replace or reuse.

d. Cut Tie--Wraps & discard (2 locations). When re- assembling, tie--wrap at same 2 locations.

e. Remove ground wire from compressor bracket (See Figure 3-33).

f.Un--plug (yellow/brown/white) from control box as- sembly.

g.Reverse above procedure for reassembly.

Cond. Motor

Ground Screw

Comp. Mounting Bolt

Figure 3-33 Condenser Motor Ground

3.6.5Evaporator Motor/Blower Assembly Removal

To remove the evaporator motor, do the following: a. Perform steps outlined in Section 3.6.2.

b. Pull back on and release the (4) locking tabs. There are 2 on each side of the control box assembly. (See Figure 3-34).

c.Lift control box assembly from lower scroll assembly, exposing evaporator motor.

d.Un--plug (black/blue/white/brown) evaporator motor from control box assembly.

e.Remove ground wire (green/yellow) from motor housing.

f.Lift motor/blower assembly from lower scroll assem- bly cradle.

g.Carefully remove the blower wheel from the evapora- tor motor shaft by pushing out from the motor side.

Blower Side Locking Tabs

Outside Locking Tabs

Figure 3-34 Evaporator Motor Locking Tabs

Lower Scroll

Assembly

Capacitor

Cradle

Figure 3-35 Evaporator Motor/Blower Assembly

In Cradle

T--298