Carrier 48TJD, TJE Typical Access Panel Locations, Outdoor-AirHood Details, Horizontal Durablade

Models: 48TJE 48TJD TJE TJF005-007 TJF004

1 52
Download 52 pages 54.01 Kb
Page 13
Image 13
Fig. 17 — Typical Access Panel Locations

OPTIONAL DURABLADE ECONOMIZER — The option- al economizer hood assembly is packaged and shipped in the fil- ter section. Damper blades and control boards are installed at the factory and the economizer is shipped in the vertical discharge position.

NOTE: Horizontal discharge block-off plate is shipped with the air hood package. If unit is to be used for vertical discharge application, discard this plate.

NOTE: Be sure to engage Durablade economizer flange under tabs in return-air opening of the unit base.

Assembly:

1.Determine if ventilation air is required in building. If so, determine the minimum amount to be supplied by each unit and record quantity of ventilation air needed for use in Step 6.

2.Remove filter access panel by raising panel and swinging panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove filter ac- cess panel. Remove outdoor-air opening panel. Save pan- els and screws. See Fig. 17. Remove optional economizer and outdoor-air damper hood package from filter section.

3.Assemble outdoor-air hood top and side plates as shown in Fig. 18. Install seal strips on hood top and sides. Put aside screen retainer and screws for later assembly. Do not attach hood to unit at this time.

4.To convert to horizontal discharge application:

a.Rotate economizer 90 degrees until the econo- mizer motor faces the condenser section (see Fig. 19).

b.Remove screws and tape from damper then rotate the barometric relief damper hinge 90 degrees. Barometric relief damper should open vertically to operate properly.

c.Install horizontal discharge block-off plate over the opening on the access panel. (Block-off plate MUST be installed before installing hood assem- bly.) See Fig. 20. Remove 12-pin blue and yellow wire jumper plug and store.

5.Insert economizer plug into economizer harness. Remove tape from barometric relief damper. See Fig. 21. Remove shipping screw (see Fig. 19).

6.If ventilation air is not required, proceed to Step 7. If ven- tilation air is required, determine the minimum position setting for required airflow. See Fig. 22. Adjust minimum position setting by adjusting the screws on the position setting bracket. Slide bracket until the top screw is in the position determined by Fig. 22. Tighten screws.

7.Remove tape from outdoor-air thermostat (OAT). Fasten OAT to inside of hood using screws and speed clips pro- vided. See Fig. 23. Make sure OAT terminals are posi- tioned up.

8.Replace outdoor-air opening panel using screws from Step 2. Replace filter access panel. Ensure the filter ac- cess panel slides along the tracks and is securely engaged.

9.Fasten hood top and side plate assembly (Fig. 18) to outdoor-air opening panel with screws provided.

10.Place knob supplied with economizer on OAT. See Fig. 23. Set OAT for 3° F below indoor room thermostat setting. If accessory enthalpy control (EC) is used in place of OAT, see instructions shipped with EC for instal- lation and adjustment. See Fig. 23.

11.Connect OAT per Fig. 24.

12.Slide outdoor-air inlet screens into screen track on hood side plate. While holding screen in place, fasten screen re- tainer to hood using screws provided.

NOTE: Refer to Fig. 25 for economizer barometric relief damper characteristics.

Fig. 17 — Typical Access Panel Locations

Fig. 18 — Outdoor-Air Hood Details

ECONOMIZER Fig. 18 — Outdoor-Air Hood DetailsFig. 19 — Horizontal Durablade

CONTROL

BOARD

BAROMETRIC Economizer Installation

RELIEF

DAMPER

ECONOMIZER

PLUG

SHIPPING

SCREW

ECONOMIZER

MOTOR

Fig. 19 — Horizontal Durablade

Economizer Installation

13

Page 13
Image 13
Carrier 48TJD, TJE Typical Access Panel Locations, Outdoor-AirHood Details, Horizontal Durablade, Economizer Installation