Table 36 — EconoMi$er Troubleshooting

PROBLEM

POTENTIAL CAUSE

REMEDY

Damper Does Not

Indoor (Evaporator) Fan is Off

Check to ensure that 24 vac is present at Terminal C1 (Common Power)

Open

 

on the IFC (Indoor [Evaporator] Fan Contactor) or that 24 vac is present at

 

 

the IFO (Indoor [Evaporator] Fan On) terminal. Check whether 24 vac is

 

 

present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is

 

 

not present, check wiring (see unit label diagram).

 

 

Check proper thermostat connection to G on the connection board.

 

No Power to EconoMi$er Controller

Check to ensure that 24 vac is present across Terminals 24 VAC and

 

 

24V COM on the EconoMi$er control. If 24 vac is not present, check wiring

 

 

(see unit label diagram). If 24 vac is present, STATUS light should be on

 

 

constantly.

 

No Power to G Terminal

If IFM is on, check to ensure 24 vac is present on G Terminal of the

 

 

EconoMi$er controller. If 24 vac is not present, check wiring (see unit

 

 

label diagram).

 

Controller Fault

If STATUS light is flashing one flash, the EconoMi$er controller is

 

 

experiencing a fault condition. Cycle power to the controller. If condition

 

 

continues, replace the EconoMi$er controller.

 

Thermostat Fault

If STATUS light is flashing two flashes, the EconoMi$er controller senses

 

 

the thermostat is wired incorrectly. Check wiring between the thermostat

 

 

and the connection board in the electrical panel. The fault condition is

 

 

caused by Y2 being energized before Y1.

 

Actuator Fault

Check the wiring between the EconoMi$er controller and the actuator.

 

 

Hold CONFIG button between 3 and 10 seconds to verify the

 

 

actuator’s operation. (This process takes 3 minutes to complete.)

EconoMi$er

Minimum Position Set Incorrectly

Verify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%)

Operation Limited to

 

to 100% to verify operation, and then set to correct setting.

Minimum Position

EconoMi$er Changeover Set Point Set Too

Set at correct value. See Table 3.

 

High or Too Low

 

 

Supply Air Temperature Sensor Faulty

If STATUS light is flashing 4 flashes, Supply Air Temperature Sensor is

 

 

faulty. Check wiring or replace sensor.

 

Outdoor Air Temperature Sensor Faulty

If STATUS light is flashing 5 flashes, Outdoor Air Temperature Sensor is

 

 

faulty. Check wiring or replace sensor.

Damper Position

Supply Air Low Limit Strategy Controlling

The supply-air temperature is less than 45 F, causing the minimum

Less than Minimum

 

position to decrease. Refer to the Start-Up instructions. Verify correct

Position Set Point

 

setting of MIN POS (%). If correct, EconoMi$er is operating correctly.

Damper Does Not

CO2 Ventilation Strategy Controlling

If a CO2 sensor is being used, and the damper position is greater than

Return to Minimum

 

minimum position, the ventilation control strategy is controlling. Refer to

Position

 

the Start-Up instructions. EconoMi$er is operating correctly.

Damper Does Not

Damper Travel is Restricted

Check to ensure the damper is not blocked.

Close on Power Loss

 

 

LEGEND

PL — Plug

48