NOTES:

1. Dimension in ( ) is in millimeters.

2.Hook rigging shackles through holes in base rail, as shown in detail ‘‘A.’’ Holes in base rails are centered around the unit cen- ter of gravity. Use wooden top skid when rigging to prevent rig- ging straps from damaging unit.

3.Unit weights do not include economizer. See Table 1 for econo- mizer weights.

All panels must be in place when rigging.

 

MAX

 

DIMENSIONS

 

 

UNIT

WEIGHT

‘‘A’’

‘‘B’’

 

‘‘C’’

 

lb

kg

in.

mm

in.

mm

 

in.

mm

48TJE,TJF004

510

231

 

 

 

 

 

 

 

48TJD,TJE,TJF005

520

236

73.69

1872

37.50

953

 

33.35

847

48TJD,TJE,TJF006

540

245

 

48TJD,TJE,TJF007

615

279

 

 

 

 

 

 

 

Fig. 5 — Rigging Details

Step 7 — Make Electrical Connections

Unit cabinet must have an uninterrupted, unbroken electri- cal ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control com- partment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA, latest edition, and local electrical codes. Do not use gas piping as an electrical ground. Fail- ure to follow this warning could result in the installer being liable for personal injury of others.

FIELD POWER SUPPLY — All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power sup- ply, the transformer must be rewired by disconnecting the black wire from the 230-v terminal wire on the transformer and con- necting it to the 200-v red terminal of the transformer.

Refer to unit label diagram for additional information. Wir- ing leads are provided for field service. Use copper conductors only when splice connectors are used.

When installing units, provide a disconnect per NEC.

All field wiring must comply with NEC and local require- ments. In Canada, electrical connections must be in accordance with CSA (Canadian Standards Association) C22.1 Canadian Electrical Code Part One.

DISCONNECT BOX LOCATION — The field-supplied dis- connect box may be mounted on the unit’s end panel or on the corner post. Mount disconnect box on the left side of the rating plate when mounting on the unit’s end panel. Do not mount the disconnect box over the unit rating plate. When mounting disconnect box on corner post, secure disconnect box to corner post and condenser coil top cover. See Fig. 7.

A disconnect box mounting space is available when an op- tional or accessory condenser coil grille is used. Mount the dis- connect on the sheet metal provided with the condenser coil grille. The sheet metal is located adjacent to the corner post on the left side of the power wiring access panel.

Install field wiring as follows:

1.Connect ground lead to chassis ground connection when using separate ground ties.

2.Install conduit between disconnect and side panel. Insert conduit through power supply knockout opening. See Fig. 9.

3.Connect power lines to power wiring leads.

4.Pigtails are provided for field power connections and are located inside the burner access panel. See Fig. 10 and 11. Use factory-supplied splices or Underwriters’ Laborato- ries (UL) approved copper connector.

5

Page 5
Image 5
Carrier TJF004, TJF005-007, 48TJD, 48TJE specifications Make Electrical Connections