Preparing the Installation Site
The first step for installing any FibreSTORE RAID system in any rack is to select an appropriate location for the rack. Use the information in Table 2 to prepare the site.
| Ciprico Rack |
| Disk | Controller | Cache Reten- | ||
|
|
|
|
| Enclosure | Enclosure | tion Unit |
|
|
|
|
| |||
Dimensions | 24" w x 77" h x 35" | 17" w x 7" h x | 17.5" w x 3.5" | 17.5" w x 3.5" | |||
| d |
|
|
| 24" d | h x 24" d | h x 18" d |
| (61 cm x 195.6 cm | (43.2 cm x | (44.5 cm x 8.9 | (44.5 cm x 8.9 | |||
| x 88.9 cm) |
| 17.8 cm x 61 | cm x 61 cm) | cm x 45.7 cm) | ||
|
|
|
|
| cm) |
|
|
|
|
|
|
|
| ||
Weight | Approximately |
| Approximately | 40 lbs (19 Kg) | 65 lbs (30 Kg) | ||
| 400 lbs (181.4 Kg) | 80 lbs (37 Kg) | with dual |
| |||
| empty; 1100 lbs |
|
| controllers |
| ||
| (499 Kg) fully |
|
|
|
| ||
| assembled |
|
|
|
| ||
|
|
|
|
|
| ||
Power | 200 - 240 VAC, |
| 100 - 120 / 200 | DC input from | 208 to 240 | ||
Requirements | 50/60 Hz, |
|
| - 240 VAC, 50 | FibreSTORE | VAC, 6.5 amp | |
| maximum 20 |
| /60 Hz, 6/3 | disk enclosure, | maximum | ||
| amps, |
|
| amps | maximum | output | |
| single phase |
|
| 60 watts |
| ||
|
|
|
|
|
|
|
|
Operating | 5° | to 40° | C (41° | to | 104° F) with 7,200 rpm drives |
| |
Temperature | 5° | to 35° | C (41° | to 95° F) with 10,000 rpm drives |
| ||
|
| ||||||
Rack Plug Type | Dual Power cords have 30A 250V plugs NEMA | ||||||
|
|
| |||||
Cooling | Approximately 10,000 BTU/hr fully assembled |
| |||||
Requirements |
|
|
|
|
|
|
|
|
|
|
| ||||
Cable Entry | Rear, at bottom of rack |
|
| ||||
|
| ||||||
Airflow | Through front of disk enclosures and out the top and back of rack | ||||||
|
|
|
|
|
|
| |
Rear clearance | 10 inches |
|
|
|
|
| |
|
|
|
|
|
|
| |
Front clearance | 6 inches |
|
|
|
|
| |
|
|
|
|
|
|
| |
Top clearance | 6 - 12" |
|
|
|
|
| |
|
| ||||||
Side clearances | Ciprico rack has side doors - approximately 2 feet when fully open | ||||||
|
|
|
|
|
| ||
|
| Table 2. Rack and Components Information |
|
10FibreSTORE RAID System: Rack Installation Guide