Low Pressure Alarm Setpoint

The setpoint at which the unit determines that there is a Low Pressure alarm condition. The Default value is -100.

Low Supply Voltage Alarm Reset

After a Low Supply Voltage alarm occurs, the setpoint at which the unit exits this condition is entered in this location. The Default is 8.0.

Low Supply Voltage Alarm Setpoint

The setpoint at which the unit determines that there is a Low Supply Voltage alarm condition. The Default is 8.5.

Low Temperature Alarm Reset

After a Low Temperature alarm occurs, the setpoint at which the unit exits this condition is entered in this location. The Default is - 80.

Low Temperature Alarm Setpoint

The setpoint at which the unit determines that there is a Low Temperature alarm condition. The Default is -100.

Meter Correction Factor

The Meter Correction Factor parameter will ordinarily be 1. The actual number is a ratio that indicates the measurement accuracy of the meter to which the device is attached. A setting of 1 indicates that the meter exhibits no measurement error. This parameter should not be changed from the default value of 1, unless the meter has been tested and its exact measurement error is known. The range is 0.95 to 1.05. The Default value is 1.

Percent CO2

This parameter reflects the content of carbon dioxide (CO2) currently present in the gas. This number should be updated only after taking an analysis. If the content is unknown, a zero (0) should be entered. The Range is 0 to 0.15 (15%). The Default is 0.

January 2002

Percent N2

This parameter reflects the content of nitrogen (N2) currently present in the gas. This number should be updated only after taking an analysis. If the content is unknown, a zero

(0)should be entered. The Range is 0 to 0.15 (15%). The Default is 0.

Percent O2

This parameter reflects the content of oxygen (O2) currently present in the gas. This number should be updated only after taking an analysis. If the content is unknown, a zero

(0)should be entered. The Range is 0 to 0.15 (15%). The Default is 0.

Pressure Corrected Pulse Enable/Disable Corrected (press only) pulses can be sent to an external device by enabling the Pulse Output Channel. The Press determines the rate at which pulses are generated. Corr. Pulse Output - CF per Pulse parameter. To enable Relay #3 for pulse output, enter a value of 35.3. An optional relay is required for the pulse output. Enter -1to disable. The Default value is -1.

Press. Corr. Pulse Output - CF per Pulse This parameter should reflect the value of the pressure (only) corrected pulse output sent from the station to an external device. For example, if each output pulse represents 1000 cubic feet, then this parameter should be set to 1000. The Default value is 1000.

Site I.D. (RUID)

The Site I.D. is unique to each device. It is the access code number that allows the user with a portable or Host computer to communicate with the unit. The Range is 1 to 65,535. The Factory Default value is 1.

Specific Gravity

Enter the specific gravity at the station. The Range is 0.554 and 2.000 inclusive. The Default value is 0.6.

C - 5