Tr o u b l e s h o o t i n g
Problem | Possible cause | Solution |
The chiller will not start. | Tripped circuit breaker. | Verify resistance to ground. Reset |
(Control not illuminated) |
| breaker. See Troubleshooting section |
|
| entitled, Checking or Resetting the |
|
| Circuit Breakers. |
| Incorrect incoming voltage. | Check incoming power source for |
|
| correct voltage and amperage as |
|
| detailed on the chiller nameplate. See |
|
| Description section entitled, |
|
| Specifications: EarthSmart ECM Series |
|
| Chillers. |
|
|
|
Pump will not start. | The power toggle switch is not turned | Turn the power toggle switch on the |
| to the “On” or “I” position. | control to the “On” or “I” position. |
| Open motor winding. | Contact Conair Service. |
| Internal overload has tripped. | |
|
| motor to cool and restart the chiller. |
| Loose wire connection or defective | Check wiring diagrams, see Appendix |
| start capacitor. | H entitled, Electrical Schematic, |
|
| replace connections or capacitor. |
| CB2 circuit breaker has been tripped. | Verify resistance to ground. Reset |
|
| breaker. See Troubleshooting section |
|
| entitled, Checking or Resetting the |
|
| Circuit Breakers. |
Troubleshooting | 6 |
|
|
Tr o u b l e s h o o t i n g l 6 - 5