INSTALLATION

Continued

CHECKING GAS CONNECTIONS

WARNING: Test all gas pip- ing and connections, internal and external to unit, for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detec- tion fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

CAUTION: Make sure exter- nal regulator has been installed between propane/LP supply and fireplace. See guidelines under Connecting Fireplace to Gas

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 23).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.

3.Check all joints from gas meter to equipment shutoff valve for natural gas or propane/LP supply to equipment shutoff valve for propane/LP (see Figures 24 or 25). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Equipment Open

Shutoff

Valve

Closed

Figure 23 - Equipment Shutoff Valve

Supply, page 15.

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1. Disconnect fireplace with its appliance main

gas valve (control valve) and equipment

shutoff valve from gas supply piping system.

Pressures in excess of 1/2 psig will damage

fireplace regulator.

Gas Control Valve

Equipment

Shutoff

Valve

Gas Meter

2.

Cap off open end of gas pipe where equipment

 

shutoff valve was connected.

3.

Pressurize supply piping system by either

 

opening propane/LP supply tank valve for

 

propane/LP gas or opening main gas valve

 

located on or near gas meter for natural gas

 

or using compressed air.

4.

Check all joints of gas supply piping system.

 

Apply noncorrosive leak detection fluid to all

 

joints. Bubbles forming show a leak.

5.

Correct all leaks at once.

6.

Reconnect fireplace and equipment shutoff

 

valve to gas supply. Check reconnected fit-

 

tings for leaks.

Figure 24 - Checking Gas Joints for

Natural Gas

Equipment Shutoff Valve

Propane/LP

Supply Tank

Gas Control Valve

Figure 25 - Checking Gas Joints for

Propane/LP Gas