INSTALLATION | WARNING ICONG 001CAUTION |
Continued | If you install the heater in a home garage |
•heater pilot and burner must be at least 18 inches above floor.
•locate heater where moving vehicle will not hit it.
For convenience and efficiency, install heater
•where there is easy access for operation, inspection, and service.
•in coldest part of room.
An optional fan kit is available from your dealer. See Accessories, page 34. If planning to use fan, locate heater near an electrical outlet.
CEILING |
|
| 36" |
6" | Minimum |
| |
Minimum |
|
From |
|
Sides Of |
|
Heater |
|
Left | Right |
Side | Side |
| 5" Minimum To Top Surface |
FLOOR | Of Carpeting, Tile Or Other |
Combustible Material |
Figure 10 - Mounting Clearances As Viewed From Front of Heater
THERMOSTAT SENSING BULB
The thermostat sensing bulb has been placed inside the heater for protection during shipping.
Locating Thermostat Sensing Bulb
1.Remove front panel of heater (see Figure 2, page 5).
2.Locate thermostat sensing bulb just under burner assembly.
IMPORTANT: Attach thermostat sensing bulb to back of heater for proper operation.
Attaching Thermostat Sensing Bulb
1.Remove thermostat sensing bulb from holders inside heater. Route through slot opening in bottom of heater.
2.Place clamp on thermostat sensing bulb as shown in Figure 11. Clamp is pro- vided in hardware package.
3.Snap clamp into upper mounting hole as shown in Figure 11. Mounting hole is located on lower left edge on back of heater. Make sure the thermostat sensing bulb is pointing up.
Thermostat
Sensing Bulb
Clamp
Continued
Figure 11 - Attaching Thermostat Sensing Bulb | 13 |