Desa (V)T36NA SERIES installation manual Venting Installation Instructions, Continued

Models: (V)T36NA SERIES

1 38
Download 38 pages 46.68 Kb
Page 10
Image 10
Horizontal Termination Configurations

10

VENTING INSTALLATION INSTRUCTIONS

Installation Planning (Cont.)

VENTING INSTALLATION INSTRUCTIONS

Continued

Minimum Pipe

Overlap 11/4"

Direct Vent

Pipe

Wall

Firestop

Maintain 1"

Minimum Air

Space Around

Outer Pipe When

Penetrating a Wall

10" x 10" Framed Opening

Siding Standoff

Screws

Manual background High Wind

Termination

Apply Mastic to

Outside Edge of

Standoff

Exterior Wall with Vinyl Siding

Manual background WARNING: Never run vent downward as this may cause excessive temperatures which could cause a fire. Operation of improperly installed and main- tained venting system could result in serious injury, property damage or loss of life.

GROUND FLOOR INSTALLATION

Recommended Applications:

Installation using cabinet surrounds

Through the wall using round or square termination (up to 12" horizontal pipe)

NOT FOR CORNER INSTALLATION

Adjustable

45° Elbow

Pipe 12" Max.

 

Horizontal High

Wind Square

Termination

Wall Firestop

Square Termination

Vertical (V)

Horizontal (H)

32" min.

17" max.

Figure 13 - Typical Horizontal Termination Cap Mounting with Additional Siding Standoff Installed

Horizontal Termination Configurations

Figures 14 through 18 show different configurations and alternatives for venting with horizontal termination. Each figure includes a chart with critical minimum and maximum dimensions which MUST be met. IMPORTANT: Remember that a horizontal run of venting must have a minimum 1/4" rise for every 12" of run toward the termination.

NOTICE: Do not seal termination cap to vent pipe. Cap must be removable for vent inspection and maintenance.

45° Elbow

 

Exterior Portion of Wall

 

 

 

 

 

 

 

Wall

 

Firestop (Round

Firestop

 

Termination Only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Round

Slide Ring

Termination

Cap

Over Elbow to

 

Complete

 

Connection

 

Round Termination

(Kit HTK Shown)

 

Figure 14 - Horizontal Termination Configuration for Square and Round Terminations

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundForManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background.Manual backgroundManual backgroundManual backgroundManual background.comManual backgroundManual backgroundManual backgroundManual backgroundManual background

111250-01C

Page 10
Image 10
Desa (V)T36NA SERIES Venting Installation Instructions, Continued, Horizontal Termination Configurations