LOCATION OF TERMINATION CAP

LOCATION OF TERMINATION CAP

N

N

D

E V

B L

 

C

 

 

Fixed

V

 

Closed

 

 

F

Openable

 

V

 

Openable

B

Fixed

Closed

H

V

B

I

G

B

B

V J X

G

A

M

V

K X

V

G V A

V TERMINATION CAP

X AIR SUPPLY INLET

G

GAS METER

RESTRICTED AREA (TERMINATION PROHIBITED)

A= clearance above grade, veranda, porch, deck, or balcony [*12 inches (30.5mc) minimum]

B= clearance to window or door that may be opened

[12 inches (30.5cm) minimum]

C = clearance to permanently closed window [minimum 12 inches (30.5cm) recommended to prevent condensation on window]

D = vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24 inches (61cm) from the center-line of the terminal [18 inches (45.7cm) minimum]

E= clearance to unventilated soffit [12 inches (30.5cm) minimum]

F= clearance to outside corner (see below)

G= clearance to inside corner (see below)

H= *not to be installed above a meter/regulator assembly within

36 inches (91.4cm) horizontally from the center-line of the regulator

I= clearance to service regulator vent outlet [*72 inches (182.9cm) minimum]

J= clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other fireplace [*12 inches (30.5cm) minimum]

K= clearance to a mechanical air supply inlet [*72 inches (182.9cm) minimum]

L= clearance above paved side-walk or a paved driveway located on public property [*84 inches (213.3cm) minimum]

M= clearance under veranda, porch, deck [*12 inches (30.5cm) minimum ]

N= clearance above a roof shall extend a minimum of 24 inches (61cm) above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18 inches (45.7cm)

vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings*

only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*

*as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A. Note: Local codes or regulations may require different clearances

Termination Clearances for Buildings with Combustible and Noncombustible Exteriors

Inside Corner

Outside Corner

A

 

 

 

A = 6" (15.2cm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V

 

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B B = 6" (15.2cm)

Recessed Location

D

C

C

E

V

Balcony with No Side Wall

G

V

G = 12" (30.5cm) minimum clearance

Balcony with Perpendicular Side Wall

H

V

J

Combustible &

Noncombustible

H = 24" (61cm)

J = 20" (50.8cm)

C = Maximum depth of 48" (121.9cm) for recessed location

D = Minimum width for back wall of recessed location - Combustible - 38" (965mm) Noncombustible - 24" (61cm)

E = Clearance from corner in recessed location- Combustible - 6" (15.2cm) Noncombustible - 2" (5.1cm)

Figure 7 - Minimum Clearances for Termination Cap

For..com

111250-01C

Page 6
Image 6
Desa (V)T36NA SERIES installation manual Location of Termination CAP, Balcony with Perpendicular Side Wall

(V)T36NA SERIES specifications

The Desa (V)T36NA SERIES represents a significant advancement in the realm of energy-efficient heating solutions, combining cutting-edge technologies with user-centric design. This series is renowned for its ability to deliver reliable heating performance while ensuring a minimal environmental impact. One of the standout features of the Desa (V)T36NA SERIES is its innovative use of high-efficiency ceramic burners. These burners not only provide superior heat output but also enhance the overall thermal efficiency of the unit, ensuring that energy consumption is kept to a minimum.

This series is equipped with a sleek, contemporary design that seamlessly fits into various home interiors. The aesthetic appeal is complemented by a range of customizable options, including different finishes and decorative elements, allowing homeowners to select a model that matches their personal style and home decor. Another notable aspect of the Desa (V)T36NA SERIES is its advanced thermostat control technology. This feature enables precise temperature regulation, ensuring consistent comfort while optimizing energy usage.

Safety is a paramount concern in the design of the Desa (V)T36NA SERIES. Each unit comes with multiple safety features, including an automatic shut-off system and a protective glass front, which provides a barrier against accidental contact. This focus on safety does not detract from the performance; rather, it enhances the user experience, providing peace of mind for families.

In terms of installation, the Desa (V)T36NA SERIES offers flexibility with venting options that cater to various home layouts. This adaptability simplifies the installation process and makes it easier to integrate the heating system into existing structures. Furthermore, these units are designed with ease of maintenance in mind, featuring accessible components that allow for straightforward servicing.

Another characteristic that sets the Desa (V)T36NA SERIES apart is its commitment to sustainability. Utilizing environmentally friendly materials and designs, this series minimizes emissions and energy consumption, aligning with modern environmental standards. Overall, the Desa (V)T36NA SERIES represents an optimal choice for discerning homeowners seeking an efficient, stylish, and reliable heating solution. With its impressive combination of features, technologies, and characteristics, this series is poised to redefine comfort and sustainability in home heating.