Electrical performance

Input

Model

 

Voltage

Frequency

 

Power Factor

 

 

 

 

 

 

 

 

 

6000L(XL)/

 

Single-phase

(46~54)/(56~64)Hz

 

>0.98 (Full load)

10000L(XL)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

Power

 

Frequency

Distortion

Overload capacity

Current

regulation

factor

 

tolerance

crest ratio

 

 

Synchronized

 

105%130% load

 

 

 

 

transfers to bypass

 

 

 

(46~54)/(56~64)Hz

 

mode after 10

 

 

 

 

in Line mode(AC

THD<3%

minutes.

 

 

±4%

0.7lag

mode)

Full load

>130% load transfers

3:1

 

 

 

 

(linear

maximum

 

 

±0.1% of normal

load)

to bypass mode after

 

 

 

frequency in

 

1 second and

 

 

 

 

Battery mode.

 

shutdown the output

 

 

 

 

 

 

after 1 minutes

 

 

 

 

 

 

 

 

 

 

Operating environment

Temperature

Humidity

Altitude

Storage temperature

 

 

 

 

0~40

<95%

<1000m

-15~40

 

 

 

 

Note: if the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated in use, please refer to the following :

Altitude (M)

1000

1500

2000

2500

3000

3500

4000

4500

5000

Deratingpower

100%

95%

91%

86%

82%

78%

74%

70%

67%

4

Page 6
Image 6
Eaton Electrical 6000L(XL), 10000L(XL) user manual Electrical performance