●Electrical performance
Input
Model |
| Voltage | Frequency |
| Power Factor | |||
|
|
|
|
|
|
|
|
|
6000L(XL)/ |
| (46~54)/(56~64)Hz |
| >0.98 (Full load) | ||||
10000L(XL) |
|
| ||||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
|
|
| Output |
|
|
|
| |
|
|
|
|
|
|
|
|
|
Voltage | Power |
| Frequency | Distortion | Overload capacity | Current | ||
regulation | factor |
| tolerance | crest ratio | ||||
|
| Synchronized |
| 105%~130% load |
| |||
|
|
| transfers to bypass |
| ||||
|
| (46~54)/(56~64)Hz |
| mode after 10 |
|
| ||
|
| in Line mode(AC | THD<3% | minutes. |
|
| ||
±4% | 0.7lag | mode) | Full load | >130% load transfers | 3:1 | |||
|
|
|
| (linear | maximum | |||
|
| ±0.1% of normal | load) | to bypass mode after |
| |||
|
| frequency in |
| 1 second and |
|
| ||
|
| Battery mode. |
| shutdown the output |
| |||
|
|
|
|
| after 1 minutes |
| ||
|
|
|
|
|
|
|
|
|
●Operating environment
Temperature | Humidity | Altitude | Storage temperature |
|
|
|
|
0℃~40℃ | <95% | <1000m | |
|
|
|
|
Note: if the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated in use, please refer to the following :
Altitude (M) | 1000 | 1500 | 2000 | 2500 | 3000 | 3500 | 4000 | 4500 | 5000 |
Deratingpower | 100% | 95% | 91% | 86% | 82% | 78% | 74% | 70% | 67% |
4