installation. The battery breaker also needs to be cut off if it is a long backup time model (XLmodel).

Open the terminal block cover located on the rear panel of the UPS, please refer to the appearance diagram.

For 6000L(XL) UPS, it is recommended to select the UL101510AWG(6mm2) wire or other insulated wire which complies with AWG Standard for the UPS input and output wirings.

For 10000L(XL) UPS, it is recommended to select the UL1015 8AWG(10mm2) wire or other insulated wire which complies with AWG Standard for the UPS input and output wirings.

Note: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed.

Connect the input and output wires to the corresponding input and output terminals according to the following diagram.

Note: you must make sure that the input and output wires and the input and output terminals are connected tightly

The protective earth ground wire refers to the wire connection between the equipment which consumes electric equipment and the ground wire. The wire diameter of protective earth ground wire should be at least as above mentioned for each model and green wire or green wire with yellow ribbon wire is used.

After having completed the installation, make sure the wiring is correct.

Please install the leak current protective breaker at the output power distribution panel of the UPS if necessary.