6
installation. The battery breaker also needs to be cut off if it is a
long backup time model (XL model).
Open the terminal block cover located on the rear panel of
the UPS, please refer to the appearance diagram.
For 6000L(XL) UPS, it is recommended to select the
UL101510AWG(6mm2) wire or other insulated wire which
complies with AWG Standard for the UPS input and output
wirings.
For 10000L(XL) UPS, it is recommended to select the
UL1015 8AWG(10mm2) wire or other insulated wire which
complies with AWG Standard for the UPS input and output
wirings.
Note: Do not use the wall receptacle as the input power source
for the UPS, as its rated current is less than the UPSs
maximum input current. Otherwise the receptacle may be
burned and destroyed.
Connect the input and output wires to the corresponding
input and output terminals according to the following
diagram.
Note: you must make sure that the input and output wires and the
input and output terminals are connected tightly
The protective earth ground wire refers to the wire
connection between the equipment which consumes electric
equipment and the ground wire. The wire diameter of
protective earth ground wire should be at least as above
mentioned for each model and green wire or green wire with
yellow ribbon wire is used.
After having completed the installation, make sure the
wiring is correct.
Please install the leak current protective breaker at the output
power distribution panel of the UPS if necessary.