Installation Drawings

Figure 9 Terminal details, Liebert Top-Terminal Battery Cabinet

See Bus

 

Termination Detail

 

Negative Term. Bus (-)

 

Positive Term. Bus (+)

 

Top View

 

+

-

Ground Bus

(See Detail)

1.75 (45)

.56

(14) 1.75 (45)

Ground Bus Detail

 

 

1.75

1.75 (45)

 

 

 

 

 

(45)

 

 

 

.53

1.75

 

 

(45)

 

 

(14)

Front View

Right Side View

 

Bus Termination Detail

* Doors And Covers Removed for Clarity

 

 

 

Notes

 

 

 

1. All dimensions are in inches (mm)

 

 

 

2.Top and bottom cable entry available through

 

 

removable access plates.

 

 

 

3. Control wiring and power wiring must be run

 

 

 

in separate conduit.

 

 

 

4. Aluminum and copper-clad aluminum cables

DO NOT DOUBLE-STACK LUGS

are not recommended.

 

 

 

5.All wiring must be in accordance with national and local electrical codes.

6.For cabinets ordered as stand-alone, the negative

and positive terminal bus does not extend to full width of battery cabinet.

7.24" minimum clearance above unit is required for air exhaust and service access.

13

Liebert® NX

Page 17
Image 17
Emerson 225-600KVA installation manual Do not DOUBLE-STACK Lugs