Emerson 225-600KVA installation manual System Composition, Clearances, Raised Floor Mounting

Models: 225-600KVA

1 40
Download 40 pages 50.89 Kb
Page 9
Image 9
1.4.2Clearances

Mechanical Installation

1.4.2Clearances

Liebert NX has no ventilation grilles at either side or at the rear of the battery system equipment. Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully opened. It is important to leave a distance of 24" (610mm) between the top of the cabinet and the ceiling of the room in which it is installed to permit adequate circulation of air coming out of the unit and for service access.

1.4.3Raised Floor Mounting

If the equipment is to be placed on a raised floor, it should be mounted on a pedestal suitably designed to accept the equipment point loading. Refer to the base view to design this pedestal.

1.5System Composition

A battery system can consist of a number of equipment cabinets, depending on the individual system design requirements, e.g., Battery Cabinet, Junction Cabinet. Refer to 3.0 - Installation Drawings for the positioning of the cabinets described below.

5

Liebert® NX

Page 9
Image 9
Emerson 225-600KVA installation manual System Composition, Clearances, Raised Floor Mounting