15

Liebert® NX

Cable Entry

See Detail A

Top View

63" (1600mm)

 

33.5" (850mm)

25.2" (640)

37.8" (960mm)

 

 

 

 

 

Front

Center of

Center of

 

Gravity

 

 

Gravity

 

76.8"

Both Sections

 

 

 

 

 

(1950mm)

 

38"

 

 

 

(965mm)

 

 

 

12.2"

14"

Bottom

18"

(311mm)

(356mm)

Cable Entry

(457mm)

 

 

See Detail B

 

Notes:

Front View

Right Side

 

 

1. All dimensions are in in [mm].

 

2.

24" minimum clearance above unit required for air exhaust.

 

3.

Keep cabinet within 15 degrees of vertical.

 

4. Top cable entry available through removable access plates.

 

5.

Control wiring and power wiring must be run in separate conduit.

6.

Width dimension is with side panels. Subtract 1.4" (35mm) for dimensions

 

with both side panels removed.

 

7.

Depth dimension includes the front door and rear panel.

 

8.

Refer to battery technical information drawing.

 

 

11.3"

 

 

 

 

 

1.8" (45mm)

(287mm)

 

 

 

 

to Panel

 

 

4.3"

Low Voltage

[110.0]

 

Cable Entry

0.9"

 

(22.7mm)

10"

 

 

(254mm)

High Voltage

 

Cable Entry

 

Front

3.6"

Detail A

(91mm)

9.4"

to Panel

3.7"

(257mm)

(95mm)

 

 

to Panel

Bottom

21.2"

Cable Entry

(538mm)

 

 

10.1"

 

(257mm) to Panel

Front

 

Detail B

Figure 11 Front Terminal Battery Cabinet outline drawing

Installation Drawings

Page 19
Image 19
Emerson 225-600KVA installation manual Top View