Emerson 225-600KVA Ground Bus Detail, Bus Termination Detail, For Pos. And Neg. Busbar

Models: 225-600KVA

1 40
Download 40 pages 50.89 Kb
Page 21
Image 21
GROUND BUS DETAIL

Installation Drawings

Figure 13 Front Terminal detail drawing

See Bus Termination

 

 

 

Detail

 

 

 

Negative Term. Bus (-)

 

 

 

Positive Term. Bus (+)

 

 

 

(+)

(-)

* Doors and covers removed for clarity

 

 

￿.56

1.75

 

 

[￿14]

[44]

FRONT

 

TYP.

 

TOP VIEW

 

 

 

(SECTION "B")

 

 

 

 

 

1.75

 

 

 

[44]

 

 

 

GROUND BUS DETAIL

Ground Bus

 

1.75

1.75

 

[45]

 

[44]

(See Detail)

 

TYP.

 

 

 

 

 

Ø.56 X .75" SLOT

 

 

 

[Ø14 X 19]

 

 

 

TYP.

 

 

 

BUS TERMINATION DETAIL

 

 

FOR POS. AND NEG. BUSBAR

RIGHT SIDE VIEW

FRONT VIEW

(SECTION "B")

NOTES:

1.All dimensions are in in [mm].

2.Top and bottom cable entry available through removable access plates.

3.Control wiring and power wiring must be run in separate conduit.

4.Aluminum and copper-clad aluminum cables are not recommended.

5.All wiring is to be in accordance with national and local electrical codes.

6.For cabinets ordered as stand-alone, the negative and positive terminal bus does not extend to full width of battery cabinet.

7.24" minimum clearance above unit is required for air exhaust and service.