Emerson 225-600KVA Right Side, Front View, 14 Typ, 1.7, Typ. Each Busbar, 1952, 1050

Models: 225-600KVA

1 40
Download 40 pages 50.89 Kb
Page 22
Image 22
Figure 14 Liebert NX Stand-Alone Junction Cabinet terminal wiring

Installation Drawings

Figure 14 Liebert NX Stand-Alone Junction Cabinet terminal wiring

.56 (14)

 

 

.56

.56

 

 

 

Typ

2.2 (55)

(14) Typ

(14) Typ

1.7 (44) X 0.7 (18)

 

 

 

 

16 Places

1.8 (45)

 

Slot 16 Places

2.2 (55)

 

 

 

16 Places

Typ. Each Busbar

 

 

 

 

 

2.2 (55)

18 Places

 

 

 

 

 

 

 

 

 

 

 

16 Places

 

 

2.2 (55)

 

 

 

 

 

 

18 Places

2.2 (55)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18 Places

 

 

 

Ground Bus

Negative Bus

Positive Bus

 

 

30.9 (785)

 

 

33.5 (805)

 

 

 

 

 

Positive

 

 

 

 

 

 

 

Bus

 

 

 

 

 

 

 

Ground

 

 

 

 

 

 

 

Bus

 

 

 

76.9

 

 

 

41.3

 

 

 

(1952)

 

 

 

 

 

 

 

 

 

(1050)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Negative

 

 

 

 

 

 

 

Bus

 

 

 

 

 

 

 

13.7

 

 

 

 

 

 

 

(348)

 

 

 

7.4

8.7

9.0

 

 

Right Side

13.6

(189)

(221)

(228)

 

 

Front View

 

 

View

(346)

 

 

 

Do not double stack lugs (two lugs on same side of busbar). This is to prevent the cables from coming into contact with other busbars.

Lugs

Bolt (14) Typ1.7 (44) X 0.7 (18)Typ. Each Busbar(1952) Busbar

DUAL LUG

CONNECTION DETAIL

Notes:

1.All dimensions are in inches (mm).

2.Control wiring and power wiring must be run in separate conduit.

3.Aluminum and copper-clad aluminum cables are not recommended.

4.Widths are without side panels. The width is 32.1" (815mm) with side panels. 5.The depth dimension includes the front door and rear panel.

Liebert® NX

18

Page 22
Image 22
Emerson 225-600KVA Right Side, Front View, Liebert NX Stand-Alone Junction Cabinet terminal wiring, 14 Typ, 1.7, 1952