1.0MECHANICAL INSTALLATION

Mechanical Installation

1.0MECHANICAL INSTALLATION

1.1Introduction

This following section describes the requirements that must be taken into account when planning the positioning and cabling of the Liebert NX battery equipment.

This chapter is a guide to general procedures and practices that should be observed by the installing engineer. The particular conditions of each site will determine the applicability of such procedures.

NOTICE

Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.

1.2Preliminary Checks

Before installing the battery equipment, please carry out the following preliminary checks:

Visually examine the equipment for transit damage, both internally and externally. Report any damage to the shipper immediately.

Verify that the correct equipment is being installed. The equipment supplied has an identification tag inside the main door.

Verify that the battery room satisfies the environmental conditions stipulated in the equipment specification, paying particular attention to the ambient temperature and air exchange system.

1.3Environmental Considerations

1.3.1Battery Room

Batteries should be mounted in an environment where the temperature is consistent and even over the whole battery. Temperature is a major factor in determining the battery life and capacity. Typical battery manufacturer performance data are quoted for an operating temperature between 68 and 77°F (20 and 25°C). Operating above this range will reduce the battery life while operation below this range will reduce the battery capacity.

Battery Temperature

In a normal installation, the battery temperature should be kept between 59 and 77°F (15°C and 25°C).

NOTE

Keep batteries away from main heat sources, main air inlets, etc.

1.3.2Storage

Should the equipment not be installed immediately, it must be stored in a room for protection against excessive humidity and heat sources (see Table 2).

NOTICE

Risk of deep discharge. Can cause permanent damage to batteries.

An unused battery must be recharged periodically as recommended by the battery manufacturer.