Instruction Manual

245364-V May 2002

Model 755A

A. Typical ALARM 1 Setting

 

 

 

 

 

 

 

40

 

 

 

 

INPUT SIGNAL

 

DEADBAND SET FOR

 

20% OF FULLSCALE

 

Percent of Fullscale 30

 

 

 

 

 

 

 

20

B. Typical ALARM 2 Setting

 

 

 

 

 

 

 

 

55

 

 

 

 

 

 

 

 

 

 

INPUT SIGNAL

 

DEADBAND SET FOR

 

10% OF FULLSCALE

 

Percent of Fullscale 50

 

 

 

 

 

 

 

45

 

 

 

 

 

 

 

When input signal moves upscale through this point, the coil of ALARM 1 relay (K1) is energized, providing continuity between the common and normally-closed contacts of the relay.

ALARM 1 Setpoint

When input signal moves downscale through this point, the coil of ALARM 1 relay (K1) is de-energized, providing continuity between the common and normally-open contacts of the relay.

When input signal moves upscale through this point, the coil of ALARM 2 relay (K2) is de-energized, providing continuity between the common and normally-open contacts of the relay.

ALARM 2 Setpoint

When input signal moves upscale through this point, the coil of ALARM 2 relay (K2) is energized, providing continuity between the common and normally-closed contacts of the relay.

Figure 2-5. Typical Alarm Settings

REQUIREMENT

TYPICAL CONNECTIONS

 

 

No. 1

NO

 

N

 

 

COM

 

H

 

 

NC

Alarm Bell

115 VAC

 

RESET

or Lamp

 

Low Alarm,

 

 

 

 

 

 

Fail-Safe

 

NO

 

 

 

 

COM

 

 

 

 

NC

 

 

 

RESET

 

 

 

No. 2

 

 

 

 

No. 1

NO

 

 

 

 

COM

 

 

 

 

NC

 

 

High Alarm,

RESET

 

 

Fail-Safe

 

NO

 

N

 

 

 

 

 

COM

 

 

 

 

H

 

 

NC

Alarm Bell

115 VAC

 

RESET

or Lamp

 

 

 

 

 

No. 2

 

 

 

 

No. 1

NO

 

 

 

 

COM

 

 

 

 

NC

 

 

Low Control

RESET

Solenoid

 

Limit,

 

 

 

 

NO

Valve

 

Fail-Safe

 

 

 

COM

 

H

 

 

 

 

 

NC

 

N

 

RESET

 

115 VAC

 

 

 

 

No. 2

 

 

 

REQUIREMENT

TYPICAL CONNECTIONS

 

 

 

 

Solenoid

 

 

No. 1

NO

Valve

 

 

 

COM

 

H

 

 

NC

 

N

 

RESET

 

115 VAC

Low Control

 

 

Limit,

 

NO

 

 

Fail-Safe

 

 

 

 

COM

 

 

 

 

 

 

 

 

NC

 

 

 

RESET

 

 

 

No. 2

 

 

 

Lower

No. 1

NO

 

N

 

COM

 

Low Alarm

 

 

H

 

 

 

Indicator,

 

NC

Alarm Bell

115 VAC

Fail-Safe

RESET

or Lamp

 

 

Solenoid

 

 

 

 

 

 

 

NO

Valve

 

Low Control,

 

COM

 

H

 

NC

 

N

Fail-Safe

RESET

 

115 VAC

 

 

 

 

No. 2

 

 

 

 

 

 

Solenoid

 

 

No. 1

NO

Valve

 

High Control,

 

COM

 

H

Fail-Safe

 

NC

 

 

 

N

 

 

 

 

RESET

 

115 VAC

 

 

 

Higher

 

NO

 

N

 

COM

 

H

High Alarm

 

 

 

NC

Alarm Bell

115 VAC

Indicator,

 

 

 

or Lamp

 

Fail-Safe

RESET

 

 

 

 

No. 2

 

 

 

Figure 2-6. Relay Terminal Connections for Typical Fail-Safe Application

2-6 Installation

Rosemount Analytical Inc. A Division of Emerson Process Management