Emerson ADTS manual Testing & Service, Manual Load Transfer, Trouble-Shooting

Models: ADTS

1 13
Download 13 pages 37.21 Kb
Page 12
Image 12

TESTING & SERVICE (continued)

MANUAL LOAD TRANSFER

This procedure will manually transfer the load if the controller is disconnected.

Do not manually operate the transfer switch until both power sources are disconnected (all conductors deenergized).

1.Deenergize both the normal and emergency source conductors (remove fuses or open circuit breakers).

2.Use the maintenance handle to manually operate the transfer switch to the opposite source. First open the closed contacts, then close the other contacts. Do not try to close both Normal and Emergency contact. See Manual Operation on page 1–3 through 1–6.

3.Then remove the maintenance handle..

Verify that the maintenance handle

has been removed before proceeding!

4.If the transfer switch is in the Emergency position manually start the engine generator and then install emergency source fuse or close the circuit breaker.

TROUBLE-SHOOTING

Note any optional accessories that may be furnished on the ADTS and review their operation. Refer to any separate drawings and/or instructions that may be packed with the ADTS.

Hazardous voltage capable of causing shock,

burns, or death is used in this switch. Do not touch the power or load terminals of the transfer switch!

Table 2-1. Trouble-Shooting Checks.

PROBLEM

CHECK IN NUMERICAL SEQUENCE

1 OPERATION

2 GEN-SET

3 VOLTAGE

 

Engine–generator set does

Hold Transfer Test switch 15

Starting control must be in the

 

not start when the Transfer

seconds or the outage must

automatic position. Batteries

 

Control switch is turned and

be long enough to allow for

must be charged and

---

held in Transfer Test position

Feature 1C time delay plus

connected. Check wiring to

 

or when normal source fails.

engine cranking and starting.

engine starting contacts.

 

 

 

 

 

Transfer switch does not

Wait for Feature 2B time delay

Generator output circuit

Voltmeter should read at least

transfer the load to the

to time out.

breaker must be closed.

90% of nominal phase to

emergency source after the

 

Generator frequency must be

phase voltage between

engine–generator set starts.

 

at least 95% of nominal (57 Hz

terminals EA and EC (or EL1

 

 

for a 60 Hz system.) *

and EL2 for 2 pole switches)*

 

 

 

 

Transfer switch does not

Wait for Feature 3A time delay

 

Voltmeter should read at least

transfer the load to normal

to time out.

 

90% of nominal phase to

source when normal returns

 

---

phase voltage between

or when the Transfer Control

 

terminals NB and NC, NC and

 

 

switch is released.

 

 

NA, and NA and NB (or NL1

 

 

 

and NL2 for 2 pole switches).

 

 

 

 

Gen. does not stop after load

Wait for Feature 2E time delay

Starting control must be in the

---

retransfer to normal source.

to time out.

automatic position.

 

 

 

 

 

* These are factory settings. Refer to Group 5 Controller User’s Guide.

If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technologies sales office or ASI: in the United States, call 1–800–800–2726 or in Canada call 1–888–234–2726. Furnish the Serial No., Catalog No., and Bill of Material (BOM) No. from the transfer switch nameplate.

2---

2

Page 12
Image 12
Emerson ADTS manual Testing & Service, Manual Load Transfer, Trouble-Shooting