Installation
Figure 16 Installing rack-mount handles
Liebert GXT3 UPS
M4 Screw, 8 pieces
9.Insert the UPS, with inner members attached, into slide rail assemblies by inserting top and bottom edges of inner members into the top and bottom, curved tracks of front members and sliding the UPS into rack, as shown in Figure 17.
Figure 17 Insert the UPS
Insert
Inner Member
NOTE
Front Member
Ends of inner members are tapered to allow rear of the UPS to be angled upward before insertion, if space allows.
The UPS should move smoothly into slide rail assemblies. If not, recheck alignment of front and rear members from Steps 4 through 6.
10.Through the rack mount handles, use M5 screws provided in this kit to secure front of the UPS to rack EIA rails to prevent the UPS from sliding out of position.
11.If optional Liebert® external battery cabinets are connected to the UPS, they can be placed all on one side of the UPS or stacked beneath the UPS. The installation procedures are the same as those of the UPS.