7.1.2Audible Alarm

Troubleshooting

7.1.2Audible Alarm

An audible alarm will be used in conjunction with the visual indicators to indicate to the user a change in UPS operating status. The audible alarm will enunciate as given in Table 9.

Table 9 Audible alarm description

Condition

Alarm

 

 

Battery discharge

half-second beep every 10 seconds

 

 

Low battery

Two half-second beeps every 5 seconds

 

 

UPS fault, load on bypass

1-second beep every 4 seconds

 

 

UPS fault, no power to load

Continuous

 

 

Overload

half-second beep every half second

 

 

Battery replacement

2-second beep every 60 seconds

 

 

Battery loss

Continuous

 

 

Wiring problem (including line-to-neutral reversal

Continuous

or a loss of proper grounding for UPS)

 

Bypass reminder

1-second beep every 2 minutes

7.2Troubleshooting

In the event of an issue with the UPS, refer to Table 10 to determine the cause and solution. If the issue persists, contact Emerson Channel Support.

Table 10

Troubleshooting

 

 

 

 

 

 

 

Problem

Cause

Solution

 

 

 

 

UPS fails to start when the

 

Ensure UPS is Off. Disconnect all loads and

 

ensure nothing is lodged in output receptacles.

On/Alarm Silence/Manual

UPS is short-circuited or overloaded

Ensure loads are not defective or shorted

Battery Test button is pressed

 

 

internally.

 

 

 

 

 

 

 

 

 

 

UPS is operating from battery mode, ensure

 

 

UPS not plugged in

UPS is securely plugged into the wall

 

 

 

receptacle.

 

 

UPS input protection circuit breaker

UPS is operating from battery mode. Save data

Battery indicator is illuminated

and close applications. Reset UPS input

has opened

 

 

breaker, then restart UPS.

 

 

 

 

 

 

 

 

 

 

UPS is operating from battery mode. Save data

 

 

Utility power is out of tolerance

and close applications. Ensure utility supply

 

 

 

voltage is within acceptable limits for UPS.

 

 

Batteries are not fully charged

Keep UPS plugged in continuously at least 24

 

 

hours to recharge batteries.

 

 

 

UPS has reduced battery

UPS is overloaded

Check load level indicator and reduce the load

on the UPS.

backup time

 

 

 

Batteries may not be able to hold a

Replace batteries. Contact your local dealer,

 

 

Emerson representative or Emerson Channel

 

 

full charge due to age

 

 

Support for replacement battery kit.

 

 

 

 

 

 

 

Fault and Bypass indicators and

 

Check load level indicator and remove non-

 

essential loads. Recalculate the load and reduce

all LED segments of battery

UPS overloaded or load is faulty

number of loads connected to UPS. Check load

level indicator are illuminated

 

 

for faults.

 

 

 

 

 

 

 

 

 

 

Ensure UPS is not overloaded, ventilation holes

Fault and Bypass indicators and

UPS shutdown due to

not blocked, or room ambient temperature is not

excessive. Wait 30 minutes to allow UPS to cool,

diagnostic A indicator are

overtemperature condition. Load is

then restart UPS. If UPS will not restart, contact

illuminated

 

on bypass power

 

your local dealer, Emerson representative or

 

 

 

 

 

 

Emerson Channel Support.

 

 

 

 