Troubleshooting
7.1.2Audible Alarm
An audible alarm will be used in conjunction with the visual indicators to indicate to the user a change in UPS operating status. The audible alarm will enunciate as given in Table 9.
Table 9 Audible alarm description
Condition | Alarm | |
|
| |
Battery discharge | ||
|
| |
Low battery | Two | |
|
| |
UPS fault, load on bypass | ||
|
| |
UPS fault, no power to load | Continuous | |
|
| |
Overload | ||
|
| |
Battery replacement | ||
|
| |
Battery loss | Continuous | |
|
| |
Wiring problem (including | Continuous | |
or a loss of proper grounding for UPS) | ||
| ||
Bypass reminder |
7.2Troubleshooting
In the event of an issue with the UPS, refer to Table 10 to determine the cause and solution. If the issue persists, contact Emerson Channel Support.
Table 10 | Troubleshooting |
|
| |
|
|
|
| |
| Problem | Cause | Solution | |
|
|
|
| |
UPS fails to start when the |
| Ensure UPS is Off. Disconnect all loads and | ||
| ensure nothing is lodged in output receptacles. | |||
On/Alarm Silence/Manual | UPS is | |||
Ensure loads are not defective or shorted | ||||
Battery Test button is pressed |
| |||
| internally. | |||
|
|
| ||
|
|
|
| |
|
|
| UPS is operating from battery mode, ensure | |
|
| UPS not plugged in | UPS is securely plugged into the wall | |
|
|
| receptacle. | |
|
| UPS input protection circuit breaker | UPS is operating from battery mode. Save data | |
Battery indicator is illuminated | and close applications. Reset UPS input | |||
has opened | ||||
|
| breaker, then restart UPS. | ||
|
|
| ||
|
|
|
| |
|
|
| UPS is operating from battery mode. Save data | |
|
| Utility power is out of tolerance | and close applications. Ensure utility supply | |
|
|
| voltage is within acceptable limits for UPS. | |
|
| Batteries are not fully charged | Keep UPS plugged in continuously at least 24 | |
|
| hours to recharge batteries. | ||
|
|
| ||
UPS has reduced battery | UPS is overloaded | Check load level indicator and reduce the load | ||
on the UPS. | ||||
backup time |
| |||
|
| Batteries may not be able to hold a | Replace batteries. Contact your local dealer, | |
|
| Emerson representative or Emerson Channel | ||
|
| full charge due to age | ||
|
| Support for replacement battery kit. | ||
|
|
| ||
|
|
|
| |
Fault and Bypass indicators and |
| Check load level indicator and remove non- | ||
| essential loads. Recalculate the load and reduce | |||
all LED segments of battery | UPS overloaded or load is faulty | |||
number of loads connected to UPS. Check load | ||||
level indicator are illuminated |
| |||
| for faults. | |||
|
|
| ||
|
|
|
| |
|
|
| Ensure UPS is not overloaded, ventilation holes | |
Fault and Bypass indicators and | UPS shutdown due to | not blocked, or room ambient temperature is not | ||
excessive. Wait 30 minutes to allow UPS to cool, | ||||
diagnostic A indicator are | overtemperature condition. Load is | |||
then restart UPS. If UPS will not restart, contact | ||||
illuminated |
| on bypass power | ||
| your local dealer, Emerson representative or | |||
|
|
| ||
|
|
| Emerson Channel Support. | |
|
|
|
|