7.0TROUBLESHOOTING

Troubleshooting

7.0TROUBLESHOOTING

This section indicates various UPS symptoms a user may encounter and troubleshooting steps in the event the UPS develops a problem. Use the following information to determine whether external factors caused the problem and how to remedy the situation.

7.1UPS Symptoms

The following symptoms indicate the Liebert® GXT3has malfunctions.

The related indicators will illuminate, indicating the UPS detected a problem.

An alarm will sound, indicating that the UPS requires attention.

7.1.1Indicators

In addition to the fault indicator being illuminated, one or more of LED segments of battery level indicator will also be illuminated to provide a diagnostic aid to the user, as shown in Figure 25. The descriptions are listed in Table 8.

Figure 25 Battery level indicator

 

 

 

 

 

 

 

 

 

 

 

 

A

B

C

D

E

 

Table 8

Indicator descriptions

 

 

 

 

 

 

 

 

 

 

 

 

Indicator

Diagnosis/Audible alarm

 

 

 

 

A - E

 

On bypass from output overload (half-second beep every half-second)

 

 

 

 

 

 

A

 

On bypass due to overtemperature condition (1-second beep every 4 seconds)

 

 

 

 

 

 

B

 

On bypass due to DC bus overvoltage (1-second beep every 4 seconds)

 

 

 

 

 

 

C

 

On bypass due to DC/DC power supply failure (1-second beep every 4 seconds)

 

 

 

 

 

 

D

 

On bypass due to PFC failure (1-second beep every 4 seconds)

 

 

 

 

 

 

E

 

On bypass due to inverter failure (1-second beep every 4 seconds)

 

 

 

 

 

 

A&B

 

UPS Failure (includes dual-fan failure, single-fan failure under certain conditions and battery

 

 

charger failure) and continuous alarm

 

 

 

A&C

 

UPS failed battery test (2-second beep every60 seconds)

 

 

 

 

 

 

A&E

 

Bypass feedback (1-second beep every 4 seconds)

 

 

 

 

 

 

 

 

 

 

 

B&E

 

Short circuit on the output

 

 

 

 

 

 

 

 

 

 

 

C&E

 

UPS shutdown by command from communication (USB port or Liebert IntelliSlotport) (no

 

 

audible)

 

 

 

 

 

Utility LED flash

L-N reverse

 

 

 

 

 

 

 

 

 

 

Battery Indicator

Battery not connected (continuous horn); check battery connection, power down and restart

Flashing

UPS

 

 

 

 

 

Bypass Indicator

Utility power voltage or frequency is out of tolerance; bypass is unavailable

Flashing

 

 

 

 

 

 

 

Indicators A - E are shown in Figure 25.

If the UPS experiences an overload, the UPS will transfer from bypass back to inverter approximately 5 minutes after the overload ends.

31