Communication
5.2USB Port Communication
The standard
5.2.1Configuration Program
Accessing the Configuration Program via USB is a new feature of the Liebert GXT3™. For most users, the factory default settings will be adequate. This section illustrates the features available for modification, as well as the factory default setting.
The USB configuration program allows these features of the Liebert GXT3 to be changed:
•Enable/Disable
•Select frequency converter operation with a fixed output frequency of 50Hz or 60Hz, bypass dis- abled
•Set the Low Battery Warning alarm time from 2 to 30 minutes
•Enable/Disable the
•Enable/Disable
•Set the wiring mode of Remote Shutdown
•Set the
•Set the
•Select the number of external battery cabinets connected to the UPS to adjust the remaining run time calculated by Liebert software products
•Select one of multiple output voltages to match various voltages, see Table 6.
Table 6 | Output voltage option |
|
| |
|
|
|
| |
|
| Factory |
| |
| UPS Model | Default, VAC | Output Voltage Option, VAC | |
120 | 110, 115, 120 and 127 | |||
|
| |||
208 | 208 / 220 / 230 / 240 | |||
|
|
|
|
NOTICE
The output voltage settings cannot be changed while the UPS is On and powering connected loads.
NOTE
For all 120V models, when the output voltage is programmed for 110VAC, the UPS will be automatically derated as follows (refer to 9.0 - Specifications for VA and watt ratings):
•500VA - 1000VA: derated to 95% of both the VA and Watt ratings
•1500VA - 3000VA: derated to 90% of both the VA and Watt ratings
NOTE
• This program is compatible with UPS models beginning with ‘GXT3’, as in ‘GXT3- 3000RT120.’ It is not compatible with earlier versions of the Liebert GXT UPS.
•A computer running Windows 2000®, XP® or Vista® is required to set up and run the configuration program.
25