Emerson GXT3, 208V user manual Specifications

Models: GXT3 208V

1 48
Download 48 pages 54.46 Kb
Page 42
Image 42
Manual background

Specifications

Table 12 Specifications of GXT3-1500RT120 - GXT3-3000RT120 and GXT3-3000RT208 UPS

 

 

 

Product Model

 

 

 

 

 

 

 

 

GXT3-1500RT120

 

GXT3-2000RT120

GXT3-3000RT120

GXT3-3000RT208

Parameters

(1500VA/1350W)

 

(2000VA/1800W)

(3000VA/2700W)

(3000VA/2700W)

Dimensions, D × W × H, in. (mm)

 

 

 

 

Unit

19.7 x 16.9 x 3.4

23.7 x 16.9 x 3.4

(497 × 430 × 85)

(602 × 430 × 85)

 

Shipping

25.5 x 23.9 x 10.6

29.4 x 23.4 x 10.6

(647 x 607 x 270)

(747 x 607 x 270)

 

Weight, lb. (kg)

 

 

 

 

 

Unit

51.1 (23.2)

 

56.1 (25.5)

71.4 (32.4)

 

 

 

 

 

Shipping

57.3 (26)

 

61.7 (28)

77 (35)

 

 

 

 

 

 

Input AC

 

 

 

 

 

 

 

 

 

 

208VAC nominal;

Voltage Range (typical)

120VAC nominal; variable based on output load

variable

 

 

 

 

 

based on output load

90 - 100% loading

 

102VAC/140VAC

 

177VAC/280VAC

70 - 90% loading

 

96VAC/140VAC

 

168VAC/280VAC

 

 

 

 

 

30 - 70% loading

 

84VAC/140VAC

 

150VAC/280VAC

 

 

 

 

 

0 - 30% loading

 

60VAC/140VAC

 

115VAC/280VAC

Frequency

 

 

40 - 70Hz; Auto Sensing

 

 

 

 

 

 

 

Input Power Cord

10 ft. attached w/

 

10 ft. attached w/

10 ft. attached w/

10 ft. attached w/

NEMA 5-15P plug

 

NEMA 5-20P plug

NEMA L5-30P plug

NEMA L6-20P plug

 

 

Output AC

 

 

 

 

 

Output Receptacles

5-15R × 6

 

5-20R × 6

L5-30R×1+5-20R×6

L6-20R×1+L6-15R×2

Voltage

110/115/120VAC (user-configurable); ±3%

208/220/230/240 VAC

(user-configurable); ±3%

 

 

 

 

 

Waveform

 

 

Sine wave

 

 

 

 

 

Utility (AC) Mode Overload

200% for 2 seconds

200% for 2 seconds

150% for 50 seconds

150% for 10 seconds

 

Battery

 

 

 

 

 

Type

 

 

Valve-regulated, nonspillable, lead acid

 

Qty×V×Rating

4 × 12V × 7.2Ah

 

4 × 12V × 9.0Ah

6 × 12V × 9.0Ah

6 × 12V × 9.0Ah

 

 

 

 

 

 

Battery Mfr./Part #

Panasonic/UP-RW1236

 

Panasonic/UP- RW1245; CSB/HR 1234W F2

 

CSB/GP 1272

 

 

 

 

Backup Time

 

 

See Table 15

 

Recharge Time

3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown

 

 

(Internal Batteries Only)

 

 

 

 

 

Environmental

 

 

 

 

 

Operating Temperature, °F (°C)

+32 to +104 (0 to 40); see Table 14 - Operating temperature parameters

Storage Temperature, °F (°C)

 

 

5 to +122 (-15 to 50)

 

 

 

 

 

 

Relative Humidity

 

 

0% to 95%, non-condensing

 

Operating Elevation

Up to 10,000 ft. (3000m) at 77ºF (25ºC) without derating

 

 

 

 

 

Storage Elevation

 

 

50,000 ft. (15000m) maximum

 

 

 

 

 

 

 

 

< 45dBA at 3ft (1m) rear

 

<48dBA max @ 3ft (1m) front and side

Audible Noise

< 46 dBA at 3ft. (1m)

 

 

<48dBA max @ 3ft. (1m) rear

 

front and side

 

 

 

 

 

 

 

 

 

 

 

 

Agency

 

 

 

 

 

Safety

 

 

UL 1778, c-UL Listed

 

RFI/EMI

 

 

FCC Part 15, Class A=CISPR22 Class B

 

 

 

 

 

 

Surge Immunity

 

 

IEC 62040-2 2nd Ed

 

 

 

 

 

 

Transportation

 

 

ISTA Procedure 1A

 

36