| Specifications | |
|
|
|
|
|
|
|
|
| |
Table 15 Battery run times (continued) |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| 208 VAC RT | |
Number of | Load Percent |
|
| 120VAC RT Models |
|
| Model | ||
|
|
|
|
|
|
| |||
Batteries/Cabinets | of Capacity | 500VA | 700VA | 1000VA | 1500VA | 2000VA | 3000VA | 3000VA | |
| 10% | 480 | 480 | 480 | 480 | 480 | 346 | 480 | |
|
|
|
|
|
|
|
|
| |
| 20% | 480 | 480 | 339 | 317 | 304 | 301 | 303 | |
|
|
|
|
|
|
|
|
| |
| 30% | 398 | 337 | 315 | 216 | 188 | 187 | 187 | |
|
|
|
|
|
|
|
|
| |
| 40% | 340 | 321 | 220 | 183 | 156 | 156 | 155 | |
Internal Battery |
|
|
|
|
|
|
|
| |
50% | 328 | 304 | 199 | 157 | 141 | 142 | 141 | ||
+ 4 External |
|
|
|
|
|
|
|
| |
60% | 316 | 217 | 167 | 145 | 126 | 127 | 126 | ||
Battery Cabinets | |||||||||
| 70% | 304 | 202 | 159 | 133 | 107 | 108 | 108 | |
|
|
|
|
|
|
|
|
| |
| 80% | 221 | 186 | 151 | 120 | 95 | 97 | 97 | |
|
|
|
|
|
|
|
|
| |
| 90% | 210 | 164 | 143 | 105 | 79 | 81 | 81 | |
|
|
|
|
|
|
|
|
| |
| 100% | 199 | 158 | 134 | 96 | 71 | 73 | 73 | |
|
|
|
|
|
|
|
|
|
Times in this table are approximate. They are based on new, fully charged batteries with 100% resistive loads and an ambient temperature of 77°F (25°C). To increase this time, turn Off
9.1Product Warranty Registration
To register for warranty protection, visit the Quick Links section of the Liebert® Web site at:
http://www.liebert.com
Click on Product Warranty Registration and fill in the form.
If you have any questions, contact Emerson Channel Support at:
North America:
Outside North America:
39