Installation and Configuration

The adjustable rack-mounting brackets (Part#: RMKIT18-32) feature retaining latches to prevent users from inadvertently sliding the UPS or battery cabinet out of the rack.

To install the rack mount brackets:

1.Unpack two rack-mounting bracket assemblies and mounting hardware from this kit. Bracket assemblies are interchangeable between left-hand or right-hand.

Remove inner member of each bracket assembly as shown at right by extending it to its outermost position, depress- ing the retaining latch and then pulling the inner member out of the bracket assembly.

2.Determine the height position inside the rack enclosure where you want to mount the UPS or battery cabinet.

! CAUTION

Reduce the risk of tipping the rack enclosure by placing the UPS or battery cabinet in the lowest possible rack position.

3. Install the rear member of each bracket assembly into the

rack enclosure with two M5 screws provided in this kit (see

figure at right). The return flanges on the bracket assembly

fit to the inside of rack mounting rails. Insert screws

loosely (finger-tight) into the top and bottom holes of the

return flange on the rear member. Extend the bracket

assembly by sliding the front member forward until it

touches the front rack mounting rail. Insert two M5 screws

loosely (finger-tight) into the top and bottom holes of the

return flange on each front member. Make sure that the

bracket assemblies are at the same mounting height on all

four (4) rack mounting rails.

4. Get eight M4 screws and eight M4 nuts from the hardware

pack in this kit. Each nut has a locking, nylon insert that

begins gripping the screw when it is halfway tight. Make

sure to tighten the nut and screw completely to ensure

locking action. Fasten the rear member and the front

member together using four screws and four nuts per

bracket assembly as shown in at right. For maximum

support, insert fasteners for each bracket assembly as far

apart as possible, depending on rack depth, while still

joining both members (see figures at right). Check

alignment of bracket assemblies and TIGHTEN ALL

SCREWS FROM Steps 2 and 3.

Retaining

Latches

Inner members

Front rack mounting rails

M5 screws

M4 nuts

457mm

(18") rack depth

M4 nuts

Return flanges

Front members

M5 screws

M4 screws

M4 nuts

M4 screws

5. Prepare the UPS or battery cabinet (the “equipment”) for

rack mounting by following instructions in the equipment’s

user manual. The equipment may require additional parts

to be added or parts to be removed for rack mounting. After

it is prepared, lay the equipment in rack-mounting

position. Fasten the inner members from Step 1 to the

equipment on both sides as shown at right with eight M4

screws provided in the kit. Make sure retaining latch is

near the rear of the equipment as shown (see figure at

right).

813mm

 

(32") rack

M4 nuts

depth

M4 screws

Retaining latch

 

UPS or battery

 

cabinet

Front

M4 screws