5.0INSTALLATION AND CONFIGURATION

Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so in 8.2 - Initial Startup and Electrical Checks.

Visually inspect the UPS for shipping damage. Report any damage to the carrier and your local dealer or Emerson representative.

! CAUTION

The UPS is heavy (see 12.0 - Specifications). Take proper precautions when lifting or moving it.

Install the Liebert® GXT3indoors in a controlled environment, where it cannot be accidentally turned off. Place it where air flows unrestricted around the unit. The installation location must be free of water, flammable liquids, gases, corrosives and conductive contaminants. Maintain a mini- mum clearance of 100mm (4 inches) in the front and rear of the UPS. Maintain an ambient tempera- ture range of 0 to 40°C (32 -104°F).

NOTE

UPS operation in sustained temperatures outside the range of 15-25°C (59°-77°F) reduces battery life.

5.1Install the Main Cabinet

The Liebert GXT3 may be installed in either a tower configuration or in a rack, depending on avail- able space and use considerations. Determine the type of installation and follow the appropriate instructions in either 5.1.1 - Tower UPS Installation or 5.1.2 - Rack-Mount UPS Installation.

5.1.1Tower UPS Installation

To install the Liebert GXT3 as a tower:

1.Take the support bases out of the accessories bag (see Figure 9).

Figure 9 Support bases

Connectors Spacers

Support Bases

2.If optional Liebert external battery cabinets will be connected to the Liebert GXT3, take out the spacers shipped with the battery cabinet.

3.Connect the spacers and the support bases as shown in Figure 9. Each Liebert GXT3 needs two assembled support bases, one in the front and one in the rear.

4.Adjust the direction of the operation and display panel and logo on the Liebert GXT3. a. Remove the front plastic bezel cover as shown in Figure 10.

Figure 10 Remove the front plastic bezel cover

Front Plastic

Bezel Cover

12

Page 18
Image 18
Emerson GXT3-6000RT208 user manual Install the Main Cabinet, Installation and Configuration, Tower UPS Installation