Specifications

12.0SPECIFICATIONS

Table 7

UPS specifications—5000, 6000, 8000 and 10,000 models

 

 

 

 

 

 

 

 

 

Model Number

GXT3-5000RT208

GXT3-6000RT208

GXT3-8000RT208

GXT3-10000RT208

 

 

 

 

 

 

 

Model Rating

4000W/5000VA

4800W/6000VA

7200W/8000VA

9000W/10000VA

 

 

 

 

 

Dimensions, Rack Mount, W x D x H

 

 

 

 

 

Unit, in. (mm)

16.9 x 26.1 x 6.8 (430 x 662 x 173)

16.9 x 26.5 x 10.3 (430 x 672 x 261)

 

 

 

 

 

Shipping, in. (mm)

26.1 x 33.1 x 13.2 (662 x 842 x 336)

24.1 x 32.8 x 16.7 (612 x 832 x 424)

 

 

 

 

 

Weight lb (kg)

 

 

 

 

 

Unit, lb (kg)

56.2 (25.5)

78.3 (35.5)

 

Shipping, lb (kg)

70.5 (32)

92.6 (42)

Input AC Parameters

 

 

 

 

 

Nominal Operating Frequency

 

50 or 60Hz (Factory Default is 60Hz)

 

 

 

 

 

 

Factory Default VAC

120/208VAC at 120 degrees

120/208VAC at 120 degrees

 

 

 

L1-L2 Factory Default Input Phase Angle

120 degrees

120 degrees

 

Allowable Input Phase Angle

120, 180, 240 degrees, auto-sensing on application of alternating current

 

(Restrictions for L-N voltages other than 120VAC)

 

 

 

Factory Default L1-N, L2-N VAC

 

120 VAC nominal

 

 

 

 

User Configurable L1-N, L2-N VAC

100/110/115/120VAC (can be modified with configuration program)

Input Frequency w/o Battery Operation

 

40 - 70 Hz

 

Input Power Connection

Hardwire Terminal Block 3W + G (L-L-N-G)

 

 

 

L1-N, L2-N Maximum Allowable VAC

 

150VAC

 

 

 

 

 

Output AC Parameters

 

 

 

 

 

Factory Default VAC

 

120/208VAC @ 120 degrees

L1-L2 Factory Default Output Phase Angle

 

120 degrees

 

Allowable Output Phase Angle

120, 180, 240 degrees, auto-sensing on initial application of input AC

 

 

 

 

 

Factory Default L1-N, L2-N VAC

 

120VAC nominal

 

 

 

 

 

User Configurable L1-N, L2-N VAC

 

100/110/115/120VAC, ±2%

 

 

 

 

 

L1-N, L2-N, Operating Load Range

 

 

 

 

 

105% to 130%

 

1 Minute

 

131% to 150%

 

10 seconds

 

 

 

 

 

151% to 200%

 

1 second

 

 

 

 

 

>200% (impact load)

 

At least 5 cycles

 

 

 

 

 

Bypass Protection Limits

 

 

 

 

 

Disable Bypass Operation

If input voltage exceeds ±15% of the nominal voltage

 

Re-Enable Bypass Operation

If input voltage returns to within ±10% of nominal output voltage

 

 

 

 

Disable Bypass Operation

When the input frequency prevents synchronous operation

 

 

 

 

 

Environmental

 

 

 

 

 

Operating Temp, °F (°C)

32 to 104 (0 to 40); see Table 9 - Operating temperature parameters

 

Storage Temp, °F (°C)

 

5 to 122 (-15 to 50)

 

Relative Humidity

 

0% to 95%, non-condensing

 

 

 

 

Operating Elevation

Up to 10,000 ft. (3000m) at 77°F (25°C) without derating

 

 

 

 

Audible Noise

less than 55dBA at 3.2ft. (1m) rear; less than 50dBA at 3.2ft. (1m) front and sides

 

 

 

 

 

Agency

 

 

 

 

 

Safety

 

UL 1778, c-UL Listed

 

RFI/EMI

FCC Part 15, Subpart B, Class A, FCC Class A

 

 

 

 

 

Surge Immunity

 

IEEE/ANSI C62.41 Category A & B

 

 

 

 

 

Transportation

 

ISTA Procedure 1A

 

 

 

 

 

 