Emerson GXT3-6000RT208 Load Level Indicators 4 Green, 1 Amber, Battery Level Indicators 5 Green

Models: GXT3-6000RT208

1 52
Download 52 pages 4.18 Kb
Page 30
Image 30

Controls and Indicators

7.3Load Level Indicators (4 Green, 1 Amber)

The load level indicator is composed of five sets of LED bars that illuminate to indicate the relative load on the UPS output in 25% increments (±5%). The load level indicator will illuminate as shown in

Figure 19.

The load level indicators display the approximate electrical load placed upon the UPS at all times.

Figure 19 Load level indicators

0 - 25%

26 - 50%

ON OFF OFF OFF OFF

ON ON OFF OFF OFF

The Liebert® GXT3 has

51 - 75%

ON ON ON OFF OFF

76 - 100%

ON ON ON ON OFF

load level indicators for Line 1 and for Line 2. One set of indicators shown for clarity.

Overload

ON ON ON ON ON

7.4Battery Level Indicators (5 Green)

The battery level indicator is composed of five sets of LED bars that illuminate and flash to indicate the battery capacity level. The Liebert® GXT3battery capacity level is shown in 20% increments (±5%). The battery level indicators will illuminate as shown in Figure 20

The battery level indicators display approximate battery capacity at all times.

The Liebert GXT3 is equipped with automatic and remote battery test features. The default setting is for the automatic test to occur every 14 days (this option is user-configurable) if utility power has not been interrupted. Should the battery fail this test, the red Fault indicator LED along with the A and C diagnostic LEDs will illuminate and an alarm will sound (refer to 11.0 - Troubleshooting). The remote test feature functions with Liebert MultiLink® and can remotely initiate the battery test.

Figure 20 Battery level indicators

 

 

Charging

 

 

0 - 20%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flash

OFF

OFF

OFF

OFF

21 - 40%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

Flash

OFF

OFF

OFF

41 - 60%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

ON

Flash

OFF

OFF

61 - 80%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

ON

ON

Flash

OFF

81 - 100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

ON

ON

ON

Flash

Fully

 

 

 

 

 

 

 

 

 

 

Charged

 

 

 

 

 

 

ON

ON

ON

ON

ON

Discharging

ON OFF OFF OFF OFF

ON ON OFF OFF OFF

ON ON ON OFF OFF

ON ON ON ON OFF

ON ON ON ON ON

ON ON ON ON ON

24

Page 30
Image 30
Emerson GXT3-6000RT208 Load Level Indicators 4 Green, 1 Amber, Battery Level Indicators 5 Green, Liebert GXT3 has